25 Amp Cable Size at 45 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 0.69V (2.87%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 0.66V (2.76%)
Voltage at Load23.3 VLine Loss: 17.2 W
Max Power & Breaker0.6 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A32.1 V (133.75%)0.0 V52.95 V (220.62%)802.5 WDrop High
2.5 mm²24 A18 A19.26 V (80.25%)4.7 V31.77 V (132.38%)481.5 WDrop High
4 mm²32 A25 A12.04 V (50.16%)12.0 V19.86 V (82.73%)300.9 WDrop High
6 mm²41 A32 A8.03 V (33.44%)16.0 V13.24 V (55.16%)200.6 WDrop High
10 mm²57 A44 A4.81 V (20.06%)19.2 V7.94 V (33.09%)120.4 WDrop High
16 mm²76 A59 A3.01 V (12.54%)21.0 V4.96 V (20.68%)75.2 WDrop High
25 mm²101 A78 A1.93 V (8.03%)22.1 V3.18 V (13.24%)48.1 WDrop High
35 mm²125 A97 A1.38 V (5.73%)22.6 V2.27 V (9.46%)34.4 WDrop High
50 mm²151 A118 A0.96 V (4.01%)23.0 V1.59 V (6.62%)24.1 W~ ≤5%
70 mm²192 A150 A0.69 V (2.87%)23.3 V1.13 V (4.73%)17.2 W✓ OK (≤3%)
95 mm²232 A181 A0.51 V (2.11%)23.5 V0.84 V (3.48%)12.7 W✓ OK (≤3%)
120 mm²269 A210 A0.4 V (1.67%)23.6 V0.66 V (2.76%)10.0 W✓ OK (≤3%)
150 mm²309 A241 A0.32 V (1.34%)23.7 V0.53 V (2.21%)8.0 W✓ OK (≤3%)
185 mm²353 A275 A0.26 V (1.08%)23.7 V0.43 V (1.79%)6.5 W✓ OK (≤3%)
240 mm²415 A324 A0.2 V (0.84%)23.8 V0.33 V (1.38%)5.0 W✓ OK (≤3%)
300 mm²477 A372 A0.16 V (0.67%)23.8 V0.26 V (1.1%)4.0 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.5%)23.9 V0.2 V (0.83%)3.0 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 45 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 25A at 45 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 25A over 45m at 24V (voltage drop: 0.69V or 2.87%).

What is the power capacity of 25A at 24V?

At unity power factor, 25A at 24V supports 0.6 kW with a standard 25A circuit breaker.