80 Amp Cable Size at 500 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)6× 400 mm²Drop: 0.71V (2.97%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.06V (29.42%)
Voltage at Load23.3 VLine Loss: 57.1 W
Max Power & Breaker1.92 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1141.33 V (4755.56%)0.0 V1882.67 V (7844.44%)91306.7 WDrop High
2.5 mm²24 A18 A684.8 V (2853.33%)0.0 V1129.6 V (4706.67%)54784.0 WDrop High
4 mm²32 A25 A428.0 V (1783.33%)0.0 V706.0 V (2941.67%)34240.0 WDrop High
6 mm²41 A32 A285.33 V (1188.89%)0.0 V470.67 V (1961.11%)22826.7 WDrop High
10 mm²57 A44 A171.2 V (713.33%)0.0 V282.4 V (1176.67%)13696.0 WDrop High
16 mm²76 A59 A107.0 V (445.83%)0.0 V176.5 V (735.42%)8560.0 WDrop High
25 mm²101 A78 A68.48 V (285.33%)0.0 V112.96 V (470.67%)5478.4 WDrop High
35 mm²125 A97 A48.91 V (203.81%)0.0 V80.69 V (336.19%)3913.1 WDrop High
50 mm²151 A118 A34.24 V (142.67%)0.0 V56.48 V (235.33%)2739.2 WDrop High
70 mm²192 A150 A24.46 V (101.9%)0.0 V40.34 V (168.1%)1956.6 WDrop High
95 mm²232 A181 A18.02 V (75.09%)6.0 V29.73 V (123.86%)1441.7 WDrop High
120 mm²269 A210 A14.27 V (59.44%)9.7 V23.53 V (98.06%)1141.3 WDrop High
150 mm²309 A241 A11.41 V (47.56%)12.6 V18.83 V (78.44%)913.1 WDrop High
185 mm²353 A275 A9.25 V (38.56%)14.7 V15.26 V (63.6%)740.3 WDrop High
240 mm²415 A324 A7.13 V (29.72%)16.9 V11.77 V (49.03%)570.7 WDrop High
300 mm²477 A372 A5.71 V (23.78%)18.3 V9.41 V (39.22%)456.5 WDrop High
400 mm²570 A445 A4.28 V (17.83%)19.7 V7.06 V (29.42%)342.4 WDrop High

FAQ — 80 Amp Cable Size at 500 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 80A at 500 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6× 400 mm² copper cable for 80A over 500m at 24V (voltage drop: 0.71V or 2.97%).

What is the power capacity of 80A at 24V?

At unity power factor, 80A at 24V supports 1.92 kW with a standard 80A circuit breaker.