90 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 90 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 11.44V (2.76%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 9.43V (2.27%)
Voltage at Load403.6 VLine Loss: 1782.9 W
Max Power & Breaker64.69 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A266.87 V (64.31%)148.1 V440.22 V (106.08%)41601.6 WDrop High
2.5 mm²24 A18 A160.12 V (38.58%)254.9 V264.13 V (63.65%)24961.0 WDrop High
4 mm²32 A25 A100.08 V (24.12%)314.9 V165.08 V (39.78%)15600.6 WDrop High
6 mm²41 A32 A66.72 V (16.08%)348.3 V110.05 V (26.52%)10400.4 WDrop High
10 mm²57 A44 A40.03 V (9.65%)375.0 V66.03 V (15.91%)6240.2 WDrop High
16 mm²76 A59 A25.02 V (6.03%)390.0 V41.27 V (9.94%)3900.2 WDrop High
25 mm²101 A78 A16.01 V (3.86%)399.0 V26.41 V (6.36%)2496.1 W~ ≤5%
35 mm²125 A97 A11.44 V (2.76%)403.6 V18.87 V (4.55%)1782.9 W✓ OK (≤3%)
50 mm²151 A118 A8.01 V (1.93%)407.0 V13.21 V (3.18%)1248.0 W✓ OK (≤3%)
70 mm²192 A150 A5.72 V (1.38%)409.3 V9.43 V (2.27%)891.5 W✓ OK (≤3%)
95 mm²232 A181 A4.21 V (1.02%)410.8 V6.95 V (1.67%)656.9 W✓ OK (≤3%)
120 mm²269 A210 A3.34 V (0.8%)411.7 V5.5 V (1.33%)520.0 W✓ OK (≤3%)
150 mm²309 A241 A2.67 V (0.64%)412.3 V4.4 V (1.06%)416.0 W✓ OK (≤3%)
185 mm²353 A275 A2.16 V (0.52%)412.8 V3.57 V (0.86%)337.3 W✓ OK (≤3%)
240 mm²415 A324 A1.67 V (0.4%)413.3 V2.75 V (0.66%)260.0 W✓ OK (≤3%)
300 mm²477 A372 A1.33 V (0.32%)413.7 V2.2 V (0.53%)208.0 W✓ OK (≤3%)
400 mm²570 A445 A1.0 V (0.24%)414.0 V1.65 V (0.4%)156.0 W✓ OK (≤3%)

FAQ — 90 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 90A at 120 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 90A over 120m at 415V (voltage drop: 11.44V or 2.76%).

What is the power capacity of 90A at 415V?

At unity power factor, 90A at 415V supports 64.69 kW with a standard 90A circuit breaker.