900 Amp Cable Size at 120 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)17× 400 mm²Drop: 0.68V (2.83%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 19.06V (79.42%)
Voltage at Load23.3 VLine Loss: 611.8 W
Max Power & Breaker21.6 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3081.6 V (12840.0%)0.0 V5083.2 V (21180.0%)2773440.0 WDrop High
2.5 mm²24 A18 A1848.96 V (7704.0%)0.0 V3049.92 V (12708.0%)1664064.0 WDrop High
4 mm²32 A25 A1155.6 V (4815.0%)0.0 V1906.2 V (7942.5%)1040040.0 WDrop High
6 mm²41 A32 A770.4 V (3210.0%)0.0 V1270.8 V (5295.0%)693360.0 WDrop High
10 mm²57 A44 A462.24 V (1926.0%)0.0 V762.48 V (3177.0%)416016.0 WDrop High
16 mm²76 A59 A288.9 V (1203.75%)0.0 V476.55 V (1985.62%)260010.0 WDrop High
25 mm²101 A78 A184.9 V (770.4%)0.0 V304.99 V (1270.8%)166406.4 WDrop High
35 mm²125 A97 A132.07 V (550.29%)0.0 V217.85 V (907.71%)118861.7 WDrop High
50 mm²151 A118 A92.45 V (385.2%)0.0 V152.5 V (635.4%)83203.2 WDrop High
70 mm²192 A150 A66.03 V (275.14%)0.0 V108.93 V (453.86%)59430.9 WDrop High
95 mm²232 A181 A48.66 V (202.74%)0.0 V80.26 V (334.42%)43791.2 WDrop High
120 mm²269 A210 A38.52 V (160.5%)0.0 V63.54 V (264.75%)34668.0 WDrop High
150 mm²309 A241 A30.82 V (128.4%)0.0 V50.83 V (211.8%)27734.4 WDrop High
185 mm²353 A275 A24.99 V (104.11%)0.0 V41.22 V (171.73%)22487.4 WDrop High
240 mm²415 A324 A19.26 V (80.25%)4.7 V31.77 V (132.38%)17334.0 WDrop High
300 mm²477 A372 A15.41 V (64.2%)8.6 V25.42 V (105.9%)13867.2 WDrop High
400 mm²570 A445 A11.56 V (48.15%)12.4 V19.06 V (79.42%)10400.4 WDrop High

FAQ — 900 Amp Cable Size at 120 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 900A at 120 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 17× 400 mm² copper cable for 900A over 120m at 24V (voltage drop: 0.68V or 2.83%).

What is the power capacity of 900A at 24V?

At unity power factor, 900A at 24V supports 21.6 kW with a standard 1000A circuit breaker.