900 Amp Cable Size at 120 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)9× 400 mm²Drop: 1.28V (2.68%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 19.06V (39.71%)
Voltage at Load46.7 VLine Loss: 1155.6 W
Max Power & Breaker43.2 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3081.6 V (6420.0%)0.0 V5083.2 V (10590.0%)2773440.0 WDrop High
2.5 mm²24 A18 A1848.96 V (3852.0%)0.0 V3049.92 V (6354.0%)1664064.0 WDrop High
4 mm²32 A25 A1155.6 V (2407.5%)0.0 V1906.2 V (3971.25%)1040040.0 WDrop High
6 mm²41 A32 A770.4 V (1605.0%)0.0 V1270.8 V (2647.5%)693360.0 WDrop High
10 mm²57 A44 A462.24 V (963.0%)0.0 V762.48 V (1588.5%)416016.0 WDrop High
16 mm²76 A59 A288.9 V (601.88%)0.0 V476.55 V (992.81%)260010.0 WDrop High
25 mm²101 A78 A184.9 V (385.2%)0.0 V304.99 V (635.4%)166406.4 WDrop High
35 mm²125 A97 A132.07 V (275.14%)0.0 V217.85 V (453.86%)118861.7 WDrop High
50 mm²151 A118 A92.45 V (192.6%)0.0 V152.5 V (317.7%)83203.2 WDrop High
70 mm²192 A150 A66.03 V (137.57%)0.0 V108.93 V (226.93%)59430.9 WDrop High
95 mm²232 A181 A48.66 V (101.37%)0.0 V80.26 V (167.21%)43791.2 WDrop High
120 mm²269 A210 A38.52 V (80.25%)9.5 V63.54 V (132.38%)34668.0 WDrop High
150 mm²309 A241 A30.82 V (64.2%)17.2 V50.83 V (105.9%)27734.4 WDrop High
185 mm²353 A275 A24.99 V (52.05%)23.0 V41.22 V (85.86%)22487.4 WDrop High
240 mm²415 A324 A19.26 V (40.12%)28.7 V31.77 V (66.19%)17334.0 WDrop High
300 mm²477 A372 A15.41 V (32.1%)32.6 V25.42 V (52.95%)13867.2 WDrop High
400 mm²570 A445 A11.56 V (24.08%)36.4 V19.06 V (39.71%)10400.4 WDrop High

FAQ — 900 Amp Cable Size at 120 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 900A at 120 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 9× 400 mm² copper cable for 900A over 120m at 48V (voltage drop: 1.28V or 2.68%).

What is the power capacity of 900A at 48V?

At unity power factor, 900A at 48V supports 43.2 kW with a standard 1000A circuit breaker.