900 Amp Cable Size at 15 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.62V (0.15%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.06V (0.52%)
Voltage at Load399.4 VLine Loss: 975.0 W
Max Power & Breaker623.54 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A333.59 V (83.4%)66.4 V550.27 V (137.57%)520020.0 WDrop High
2.5 mm²24 A18 A200.16 V (50.04%)199.8 V330.16 V (82.54%)312012.0 WDrop High
4 mm²32 A25 A125.1 V (31.27%)274.9 V206.35 V (51.59%)195007.5 WDrop High
6 mm²41 A32 A83.4 V (20.85%)316.6 V137.57 V (34.39%)130005.0 WDrop High
10 mm²57 A44 A50.04 V (12.51%)350.0 V82.54 V (20.64%)78003.0 WDrop High
16 mm²76 A59 A31.27 V (7.82%)368.7 V51.59 V (12.9%)48751.9 WDrop High
25 mm²101 A78 A20.02 V (5.0%)380.0 V33.02 V (8.25%)31201.2 WDrop High
35 mm²125 A97 A14.3 V (3.57%)385.7 V23.58 V (5.9%)22286.6 WDrop High
50 mm²151 A118 A10.01 V (2.5%)390.0 V16.51 V (4.13%)15600.6 WDrop High
70 mm²192 A150 A7.15 V (1.79%)392.9 V11.79 V (2.95%)11143.3 WDrop High
95 mm²232 A181 A5.27 V (1.32%)394.7 V8.69 V (2.17%)8210.8 WDrop High
120 mm²269 A210 A4.17 V (1.04%)395.8 V6.88 V (1.72%)6500.2 WDrop High
150 mm²309 A241 A3.34 V (0.83%)396.7 V5.5 V (1.38%)5200.2 WDrop High
185 mm²353 A275 A2.7 V (0.68%)397.3 V4.46 V (1.12%)4216.4 WDrop High
240 mm²415 A324 A2.08 V (0.52%)397.9 V3.44 V (0.86%)3250.1 WDrop High
300 mm²477 A372 A1.67 V (0.42%)398.3 V2.75 V (0.69%)2600.1 WDrop High
400 mm²570 A445 A1.25 V (0.31%)398.7 V2.06 V (0.52%)1950.1 WDrop High

FAQ — 900 Amp Cable Size at 15 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 900A at 15 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 15m at 400V (voltage drop: 0.62V or 0.15%).

What is the power capacity of 900A at 400V?

At unity power factor, 900A at 400V supports 623.54 kW with a standard 1000A circuit breaker.