900 Amp Cable Size at 50 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.08V (0.52%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.88V (1.72%)
Voltage at Load397.9 VLine Loss: 3250.1 W
Max Power & Breaker623.54 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1111.98 V (277.99%)0.0 V1834.24 V (458.56%)1733400.0 WDrop High
2.5 mm²24 A18 A667.19 V (166.8%)0.0 V1100.55 V (275.14%)1040040.0 WDrop High
4 mm²32 A25 A416.99 V (104.25%)0.0 V687.84 V (171.96%)650025.0 WDrop High
6 mm²41 A32 A277.99 V (69.5%)122.0 V458.56 V (114.64%)433350.0 WDrop High
10 mm²57 A44 A166.8 V (41.7%)233.2 V275.14 V (68.78%)260010.0 WDrop High
16 mm²76 A59 A104.25 V (26.06%)295.8 V171.96 V (42.99%)162506.2 WDrop High
25 mm²101 A78 A66.72 V (16.68%)333.3 V110.05 V (27.51%)104004.0 WDrop High
35 mm²125 A97 A47.66 V (11.91%)352.3 V78.61 V (19.65%)74288.6 WDrop High
50 mm²151 A118 A33.36 V (8.34%)366.6 V55.03 V (13.76%)52002.0 WDrop High
70 mm²192 A150 A23.83 V (5.96%)376.2 V39.31 V (9.83%)37144.3 WDrop High
95 mm²232 A181 A17.56 V (4.39%)382.4 V28.96 V (7.24%)27369.5 WDrop High
120 mm²269 A210 A13.9 V (3.47%)386.1 V22.93 V (5.73%)21667.5 WDrop High
150 mm²309 A241 A11.12 V (2.78%)388.9 V18.34 V (4.59%)17334.0 WDrop High
185 mm²353 A275 A9.02 V (2.25%)391.0 V14.87 V (3.72%)14054.6 WDrop High
240 mm²415 A324 A6.95 V (1.74%)393.1 V11.46 V (2.87%)10833.7 WDrop High
300 mm²477 A372 A5.56 V (1.39%)394.4 V9.17 V (2.29%)8667.0 WDrop High
400 mm²570 A445 A4.17 V (1.04%)395.8 V6.88 V (1.72%)6500.2 WDrop High

FAQ — 900 Amp Cable Size at 50 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 900A at 50 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 50m at 400V (voltage drop: 2.08V or 0.52%).

What is the power capacity of 900A at 400V?

At unity power factor, 900A at 400V supports 623.54 kW with a standard 1000A circuit breaker.