Kabeltværsnit for 10 Ampere ved 35 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 10 A over 35 m ved 400V.
Copper Cable (≤3% Drop)1.5 mm²Drop: 8.65V (2.16%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 8.56V (2.14%)
Voltage at Load391.4 VLine Loss: 149.8 W
Max Power & Breaker6.93 kW10A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 8.65 V (2.16%) | 391.4 V | 14.27 V (3.57%) | 149.8 W | ✓ OK (≤3%) |
| 2.5 mm² | 24 A | 18 A | 5.19 V (1.3%) | 394.8 V | 8.56 V (2.14%) | 89.9 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 3.24 V (0.81%) | 396.8 V | 5.35 V (1.34%) | 56.2 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 2.16 V (0.54%) | 397.8 V | 3.57 V (0.89%) | 37.5 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 1.3 V (0.32%) | 398.7 V | 2.14 V (0.53%) | 22.5 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.81 V (0.2%) | 399.2 V | 1.34 V (0.33%) | 14.0 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.52 V (0.13%) | 399.5 V | 0.86 V (0.21%) | 9.0 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.37 V (0.09%) | 399.6 V | 0.61 V (0.15%) | 6.4 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.26 V (0.06%) | 399.7 V | 0.43 V (0.11%) | 4.5 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.19 V (0.05%) | 399.8 V | 0.31 V (0.08%) | 3.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.14 V (0.03%) | 399.9 V | 0.23 V (0.06%) | 2.4 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.11 V (0.03%) | 399.9 V | 0.18 V (0.04%) | 1.9 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.09 V (0.02%) | 399.9 V | 0.14 V (0.04%) | 1.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.07 V (0.02%) | 399.9 V | 0.12 V (0.03%) | 1.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.05 V (0.01%) | 399.9 V | 0.09 V (0.02%) | 0.9 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.04 V (0.01%) | 400.0 V | 0.07 V (0.02%) | 0.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.03 V (0.01%) | 400.0 V | 0.05 V (0.01%) | 0.6 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 10 Ampere ved 35 Meter (400V)
Hvilket kabeltværsnit kræves til 10A ved 35 meter (400V)?
Til 10 Ampere over 35 meter ved 400V anbefales 1.5 mm² kobberkabel (spændingsfald 8.65V / 2.16%).
Hvor mange kW svarer 10A ved 400V til?
Det svarer til 6.93 kW med en anbefalet sikring på 10A.
Related Lengths & Currents (400V)
10A · 5m (400V)10A · 10m (400V)10A · 15m (400V)10A · 20m (400V)10A · 25m (400V)10A · 30m (400V)10A · 40m (400V)10A · 45m (400V)10A · 50m (400V)10A · 60m (400V)10A · 70m (400V)16A · 35m (400V)20A · 35m (400V)25A · 35m (400V)32A · 35m (400V)40A · 35m (400V)50A · 35m (400V)63A · 35m (400V)80A · 35m (400V)100A · 35m (400V)125A · 35m (400V)160A · 35m (400V)200A · 35m (400V)