Kabeltværsnit for 10 Ampere ved 60 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 10 A over 60 m ved 400V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 8.9V (2.22%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 9.17V (2.29%)
Voltage at Load391.1 VLine Loss: 154.1 W
Max Power & Breaker6.93 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A14.83 V (3.71%)385.2 V24.46 V (6.11%)256.8 W~ ≤5%
2.5 mm²24 A18 A8.9 V (2.22%)391.1 V14.67 V (3.67%)154.1 W✓ OK (≤3%)
4 mm²32 A25 A5.56 V (1.39%)394.4 V9.17 V (2.29%)96.3 W✓ OK (≤3%)
6 mm²41 A32 A3.71 V (0.93%)396.3 V6.11 V (1.53%)64.2 W✓ OK (≤3%)
10 mm²57 A44 A2.22 V (0.56%)397.8 V3.67 V (0.92%)38.5 W✓ OK (≤3%)
16 mm²76 A59 A1.39 V (0.35%)398.6 V2.29 V (0.57%)24.1 W✓ OK (≤3%)
25 mm²101 A78 A0.89 V (0.22%)399.1 V1.47 V (0.37%)15.4 W✓ OK (≤3%)
35 mm²125 A97 A0.64 V (0.16%)399.4 V1.05 V (0.26%)11.0 W✓ OK (≤3%)
50 mm²151 A118 A0.44 V (0.11%)399.6 V0.73 V (0.18%)7.7 W✓ OK (≤3%)
70 mm²192 A150 A0.32 V (0.08%)399.7 V0.52 V (0.13%)5.5 W✓ OK (≤3%)
95 mm²232 A181 A0.23 V (0.06%)399.8 V0.39 V (0.1%)4.1 W✓ OK (≤3%)
120 mm²269 A210 A0.19 V (0.05%)399.8 V0.31 V (0.08%)3.2 W✓ OK (≤3%)
150 mm²309 A241 A0.15 V (0.04%)399.9 V0.24 V (0.06%)2.6 W✓ OK (≤3%)
185 mm²353 A275 A0.12 V (0.03%)399.9 V0.2 V (0.05%)2.1 W✓ OK (≤3%)
240 mm²415 A324 A0.09 V (0.02%)399.9 V0.15 V (0.04%)1.6 W✓ OK (≤3%)
300 mm²477 A372 A0.07 V (0.02%)399.9 V0.12 V (0.03%)1.3 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.01%)399.9 V0.09 V (0.02%)1.0 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 10 Ampere ved 60 Meter (400V)

Hvilket kabeltværsnit kræves til 10A ved 60 meter (400V)?

Til 10 Ampere over 60 meter ved 400V anbefales 2.5 mm² kobberkabel (spændingsfald 8.9V / 2.22%).

Hvor mange kW svarer 10A ved 400V til?

Det svarer til 6.93 kW med en anbefalet sikring på 10A.