Kabeltværsnit for 16 Ampere ved 35 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 16 A over 35 m ved 400V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 8.3V (2.08%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 8.56V (2.14%)
Voltage at Load391.7 VLine Loss: 230.1 W
Max Power & Breaker11.09 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A13.84 V (3.46%)386.2 V22.83 V (5.71%)383.5 W~ ≤5%
2.5 mm²24 A18 A8.3 V (2.08%)391.7 V13.7 V (3.42%)230.1 W✓ OK (≤3%)
4 mm²32 A25 A5.19 V (1.3%)394.8 V8.56 V (2.14%)143.8 W✓ OK (≤3%)
6 mm²41 A32 A3.46 V (0.86%)396.5 V5.71 V (1.43%)95.9 W✓ OK (≤3%)
10 mm²57 A44 A2.08 V (0.52%)397.9 V3.42 V (0.86%)57.5 W✓ OK (≤3%)
16 mm²76 A59 A1.3 V (0.32%)398.7 V2.14 V (0.53%)36.0 W✓ OK (≤3%)
25 mm²101 A78 A0.83 V (0.21%)399.2 V1.37 V (0.34%)23.0 W✓ OK (≤3%)
35 mm²125 A97 A0.59 V (0.15%)399.4 V0.98 V (0.24%)16.4 W✓ OK (≤3%)
50 mm²151 A118 A0.42 V (0.1%)399.6 V0.68 V (0.17%)11.5 W✓ OK (≤3%)
70 mm²192 A150 A0.3 V (0.07%)399.7 V0.49 V (0.12%)8.2 W✓ OK (≤3%)
95 mm²232 A181 A0.22 V (0.05%)399.8 V0.36 V (0.09%)6.1 W✓ OK (≤3%)
120 mm²269 A210 A0.17 V (0.04%)399.8 V0.29 V (0.07%)4.8 W✓ OK (≤3%)
150 mm²309 A241 A0.14 V (0.03%)399.9 V0.23 V (0.06%)3.8 W✓ OK (≤3%)
185 mm²353 A275 A0.11 V (0.03%)399.9 V0.19 V (0.05%)3.1 W✓ OK (≤3%)
240 mm²415 A324 A0.09 V (0.02%)399.9 V0.14 V (0.04%)2.4 W✓ OK (≤3%)
300 mm²477 A372 A0.07 V (0.02%)399.9 V0.11 V (0.03%)1.9 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.01%)399.9 V0.09 V (0.02%)1.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 16 Ampere ved 35 Meter (400V)

Hvilket kabeltværsnit kræves til 16A ved 35 meter (400V)?

Til 16 Ampere over 35 meter ved 400V anbefales 2.5 mm² kobberkabel (spændingsfald 8.3V / 2.08%).

Hvor mange kW svarer 16A ved 400V til?

Det svarer til 11.09 kW med en anbefalet sikring på 16A.