Kabeltværsnit for 40 Ampere ved 60 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 40 A over 60 m ved 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 8.9V (2.22%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 9.17V (2.29%)
Voltage at Load391.1 VLine Loss: 616.3 W
Max Power & Breaker27.71 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A59.31 V (14.83%)340.7 V97.83 V (24.46%)4108.8 WDrop High
2.5 mm²24 A18 A35.58 V (8.9%)364.4 V58.7 V (14.67%)2465.3 WDrop High
4 mm²32 A25 A22.24 V (5.56%)377.8 V36.68 V (9.17%)1540.8 WDrop High
6 mm²41 A32 A14.83 V (3.71%)385.2 V24.46 V (6.11%)1027.2 W~ ≤5%
10 mm²57 A44 A8.9 V (2.22%)391.1 V14.67 V (3.67%)616.3 W✓ OK (≤3%)
16 mm²76 A59 A5.56 V (1.39%)394.4 V9.17 V (2.29%)385.2 W✓ OK (≤3%)
25 mm²101 A78 A3.56 V (0.89%)396.4 V5.87 V (1.47%)246.5 W✓ OK (≤3%)
35 mm²125 A97 A2.54 V (0.64%)397.5 V4.19 V (1.05%)176.1 W✓ OK (≤3%)
50 mm²151 A118 A1.78 V (0.44%)398.2 V2.93 V (0.73%)123.3 W✓ OK (≤3%)
70 mm²192 A150 A1.27 V (0.32%)398.7 V2.1 V (0.52%)88.0 W✓ OK (≤3%)
95 mm²232 A181 A0.94 V (0.23%)399.1 V1.54 V (0.39%)64.9 W✓ OK (≤3%)
120 mm²269 A210 A0.74 V (0.19%)399.3 V1.22 V (0.31%)51.4 W✓ OK (≤3%)
150 mm²309 A241 A0.59 V (0.15%)399.4 V0.98 V (0.24%)41.1 W✓ OK (≤3%)
185 mm²353 A275 A0.48 V (0.12%)399.5 V0.79 V (0.2%)33.3 W✓ OK (≤3%)
240 mm²415 A324 A0.37 V (0.09%)399.6 V0.61 V (0.15%)25.7 W✓ OK (≤3%)
300 mm²477 A372 A0.3 V (0.07%)399.7 V0.49 V (0.12%)20.5 W✓ OK (≤3%)
400 mm²570 A445 A0.22 V (0.06%)399.8 V0.37 V (0.09%)15.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 40 Ampere ved 60 Meter (400V)

Hvilket kabeltværsnit kræves til 40A ved 60 meter (400V)?

Til 40 Ampere over 60 meter ved 400V anbefales 10 mm² kobberkabel (spændingsfald 8.9V / 2.22%).

Hvor mange kW svarer 40A ved 400V til?

Det svarer til 27.71 kW med en anbefalet sikring på 40A.