Kabeltværsnit for 32 Ampere ved 10 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 32 A over 10 m ved 230V.

Copper Cable (≤3% Drop)4 mm²Drop: 3.42V (1.49%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 3.77V (1.64%)
Voltage at Load226.6 VLine Loss: 109.6 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9.13 V (3.97%)220.9 V15.06 V (6.55%)292.2 WDrop High
2.5 mm²24 A18 A5.48 V (2.38%)224.5 V9.04 V (3.93%)175.3 WDrop High
4 mm²32 A25 A3.42 V (1.49%)226.6 V5.65 V (2.46%)109.6 W✓ OK (≤3%)
6 mm²41 A32 A2.28 V (0.99%)227.7 V3.77 V (1.64%)73.0 W✓ OK (≤3%)
10 mm²57 A44 A1.37 V (0.6%)228.6 V2.26 V (0.98%)43.8 W✓ OK (≤3%)
16 mm²76 A59 A0.86 V (0.37%)229.1 V1.41 V (0.61%)27.4 W✓ OK (≤3%)
25 mm²101 A78 A0.55 V (0.24%)229.5 V0.9 V (0.39%)17.5 W✓ OK (≤3%)
35 mm²125 A97 A0.39 V (0.17%)229.6 V0.65 V (0.28%)12.5 W✓ OK (≤3%)
50 mm²151 A118 A0.27 V (0.12%)229.7 V0.45 V (0.2%)8.8 W✓ OK (≤3%)
70 mm²192 A150 A0.2 V (0.09%)229.8 V0.32 V (0.14%)6.3 W✓ OK (≤3%)
95 mm²232 A181 A0.14 V (0.06%)229.9 V0.24 V (0.1%)4.6 W✓ OK (≤3%)
120 mm²269 A210 A0.11 V (0.05%)229.9 V0.19 V (0.08%)3.7 W✓ OK (≤3%)
150 mm²309 A241 A0.09 V (0.04%)229.9 V0.15 V (0.07%)2.9 W✓ OK (≤3%)
185 mm²353 A275 A0.07 V (0.03%)229.9 V0.12 V (0.05%)2.4 W✓ OK (≤3%)
240 mm²415 A324 A0.06 V (0.02%)229.9 V0.09 V (0.04%)1.8 W✓ OK (≤3%)
300 mm²477 A372 A0.05 V (0.02%)230.0 V0.08 V (0.03%)1.5 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.01%)230.0 V0.06 V (0.02%)1.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 32 Ampere ved 10 Meter (230V)

Hvilket kabeltværsnit kræves til 32A ved 10 meter (230V)?

Til 32 Ampere over 10 meter ved 230V anbefales 4 mm² kobberkabel (spændingsfald 3.42V / 1.49%).

Hvor mange kW svarer 32A ved 230V til?

Det svarer til 7.36 kW med en anbefalet sikring på 32A.