Kabeltværsnit for 10 Ampere ved 10 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 10 A over 10 m ved 230V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 2.85V (1.24%)
Aluminum Cable (≤3% Drop)1.5 mm²Drop: 4.71V (2.05%)
Voltage at Load227.1 VLine Loss: 28.5 W
Max Power & Breaker2.3 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2.85 V (1.24%)227.1 V4.71 V (2.05%)28.5 W✓ OK (≤3%)
2.5 mm²24 A18 A1.71 V (0.74%)228.3 V2.82 V (1.23%)17.1 W✓ OK (≤3%)
4 mm²32 A25 A1.07 V (0.47%)228.9 V1.76 V (0.77%)10.7 W✓ OK (≤3%)
6 mm²41 A32 A0.71 V (0.31%)229.3 V1.18 V (0.51%)7.1 W✓ OK (≤3%)
10 mm²57 A44 A0.43 V (0.19%)229.6 V0.71 V (0.31%)4.3 W✓ OK (≤3%)
16 mm²76 A59 A0.27 V (0.12%)229.7 V0.44 V (0.19%)2.7 W✓ OK (≤3%)
25 mm²101 A78 A0.17 V (0.07%)229.8 V0.28 V (0.12%)1.7 W✓ OK (≤3%)
35 mm²125 A97 A0.12 V (0.05%)229.9 V0.2 V (0.09%)1.2 W✓ OK (≤3%)
50 mm²151 A118 A0.09 V (0.04%)229.9 V0.14 V (0.06%)0.9 W✓ OK (≤3%)
70 mm²192 A150 A0.06 V (0.03%)229.9 V0.1 V (0.04%)0.6 W✓ OK (≤3%)
95 mm²232 A181 A0.05 V (0.02%)230.0 V0.07 V (0.03%)0.5 W✓ OK (≤3%)
120 mm²269 A210 A0.04 V (0.02%)230.0 V0.06 V (0.03%)0.4 W✓ OK (≤3%)
150 mm²309 A241 A0.03 V (0.01%)230.0 V0.05 V (0.02%)0.3 W✓ OK (≤3%)
185 mm²353 A275 A0.02 V (0.01%)230.0 V0.04 V (0.02%)0.2 W✓ OK (≤3%)
240 mm²415 A324 A0.02 V (0.01%)230.0 V0.03 V (0.01%)0.2 W✓ OK (≤3%)
300 mm²477 A372 A0.01 V (0.01%)230.0 V0.02 V (0.01%)0.1 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.0%)230.0 V0.02 V (0.01%)0.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 10 Ampere ved 10 Meter (230V)

Hvilket kabeltværsnit kræves til 10A ved 10 meter (230V)?

Til 10 Ampere over 10 meter ved 230V anbefales 1.5 mm² kobberkabel (spændingsfald 2.85V / 1.24%).

Hvor mange kW svarer 10A ved 230V til?

Det svarer til 2.3 kW med en anbefalet sikring på 10A.