Kabeltværsnit for 125 Ampere ved 100 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 125 A over 100 m ved 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 5.63V (2.45%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 5.88V (2.56%)
Voltage at Load224.4 VLine Loss: 703.9 W
Max Power & Breaker28.75 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A356.67 V (155.07%)0.0 V588.33 V (255.8%)44583.3 WDrop High
2.5 mm²24 A18 A214.0 V (93.04%)16.0 V353.0 V (153.48%)26750.0 WDrop High
4 mm²32 A25 A133.75 V (58.15%)96.3 V220.62 V (95.92%)16718.7 WDrop High
6 mm²41 A32 A89.17 V (38.77%)140.8 V147.08 V (63.95%)11145.8 WDrop High
10 mm²57 A44 A53.5 V (23.26%)176.5 V88.25 V (38.37%)6687.5 WDrop High
16 mm²76 A59 A33.44 V (14.54%)196.6 V55.16 V (23.98%)4179.7 WDrop High
25 mm²101 A78 A21.4 V (9.3%)208.6 V35.3 V (15.35%)2675.0 WDrop High
35 mm²125 A97 A15.29 V (6.65%)214.7 V25.21 V (10.96%)1910.7 WDrop High
50 mm²151 A118 A10.7 V (4.65%)219.3 V17.65 V (7.67%)1337.5 W~ ≤5%
70 mm²192 A150 A7.64 V (3.32%)222.4 V12.61 V (5.48%)955.4 W~ ≤5%
95 mm²232 A181 A5.63 V (2.45%)224.4 V9.29 V (4.04%)703.9 W✓ OK (≤3%)
120 mm²269 A210 A4.46 V (1.94%)225.5 V7.35 V (3.2%)557.3 W✓ OK (≤3%)
150 mm²309 A241 A3.57 V (1.55%)226.4 V5.88 V (2.56%)445.8 W✓ OK (≤3%)
185 mm²353 A275 A2.89 V (1.26%)227.1 V4.77 V (2.07%)361.5 W✓ OK (≤3%)
240 mm²415 A324 A2.23 V (0.97%)227.8 V3.68 V (1.6%)278.6 W✓ OK (≤3%)
300 mm²477 A372 A1.78 V (0.78%)228.2 V2.94 V (1.28%)222.9 W✓ OK (≤3%)
400 mm²570 A445 A1.34 V (0.58%)228.7 V2.21 V (0.96%)167.2 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 125 Ampere ved 100 Meter (230V)

Hvilket kabeltværsnit kræves til 125A ved 100 meter (230V)?

Til 125 Ampere over 100 meter ved 230V anbefales 95 mm² kobberkabel (spændingsfald 5.63V / 2.45%).

Hvor mange kW svarer 125A ved 230V til?

Det svarer til 28.75 kW med en anbefalet sikring på 125A.