⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 25 Ampere ved 100 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 25 A over 100 m ved 230V.

Copper Cable (≤3% Drop)16 mm²Drop: 6.69V (2.91%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 5.04V (2.19%)
Voltage at Load223.3 VLine Loss: 167.2 W
Max Power & Breaker5.75 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A71.33 V (31.01%)158.7 V117.67 V (51.16%)1783.3 WDrop High
2.5 mm²24 A18 A42.8 V (18.61%)187.2 V70.6 V (30.7%)1070.0 WDrop High
4 mm²32 A25 A26.75 V (11.63%)203.2 V44.12 V (19.18%)668.7 WDrop High
6 mm²41 A32 A17.83 V (7.75%)212.2 V29.42 V (12.79%)445.8 WDrop High
10 mm²57 A44 A10.7 V (4.65%)219.3 V17.65 V (7.67%)267.5 W~ ≤5%
16 mm²76 A59 A6.69 V (2.91%)223.3 V11.03 V (4.8%)167.2 W✓ OK (≤3%)
25 mm²101 A78 A4.28 V (1.86%)225.7 V7.06 V (3.07%)107.0 W✓ OK (≤3%)
35 mm²125 A97 A3.06 V (1.33%)226.9 V5.04 V (2.19%)76.4 W✓ OK (≤3%)
50 mm²151 A118 A2.14 V (0.93%)227.9 V3.53 V (1.53%)53.5 W✓ OK (≤3%)
70 mm²192 A150 A1.53 V (0.66%)228.5 V2.52 V (1.1%)38.2 W✓ OK (≤3%)
95 mm²232 A181 A1.13 V (0.49%)228.9 V1.86 V (0.81%)28.2 W✓ OK (≤3%)
120 mm²269 A210 A0.89 V (0.39%)229.1 V1.47 V (0.64%)22.3 W✓ OK (≤3%)
150 mm²309 A241 A0.71 V (0.31%)229.3 V1.18 V (0.51%)17.8 W✓ OK (≤3%)
185 mm²353 A275 A0.58 V (0.25%)229.4 V0.95 V (0.41%)14.5 W✓ OK (≤3%)
240 mm²415 A324 A0.45 V (0.19%)229.6 V0.74 V (0.32%)11.1 W✓ OK (≤3%)
300 mm²477 A372 A0.36 V (0.16%)229.6 V0.59 V (0.26%)8.9 W✓ OK (≤3%)
400 mm²570 A445 A0.27 V (0.12%)229.7 V0.44 V (0.19%)6.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 25 Ampere ved 100 Meter (230V)

Hvilket kabeltværsnit kræves til 25A ved 100 meter (230V)?

Til 25 Ampere over 100 meter ved 230V anbefales 16 mm² kobberkabel (spændingsfald 6.69V / 2.91%).

Hvor mange kW svarer 25A ved 230V til?

Det svarer til 5.75 kW med en anbefalet sikring på 25A.