Kabeltværsnit for 15 Ampere ved 45 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 15 A over 45 m ved 230V.

Copper Cable (≤3% Drop)6 mm²Drop: 4.82V (2.09%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 4.77V (2.07%)
Voltage at Load225.2 VLine Loss: 72.2 W
Max Power & Breaker3.45 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A19.26 V (8.37%)210.7 V31.77 V (13.81%)288.9 WDrop High
2.5 mm²24 A18 A11.56 V (5.02%)218.4 V19.06 V (8.29%)173.3 WDrop High
4 mm²32 A25 A7.22 V (3.14%)222.8 V11.91 V (5.18%)108.3 W~ ≤5%
6 mm²41 A32 A4.82 V (2.09%)225.2 V7.94 V (3.45%)72.2 W✓ OK (≤3%)
10 mm²57 A44 A2.89 V (1.26%)227.1 V4.77 V (2.07%)43.3 W✓ OK (≤3%)
16 mm²76 A59 A1.81 V (0.79%)228.2 V2.98 V (1.29%)27.1 W✓ OK (≤3%)
25 mm²101 A78 A1.16 V (0.5%)228.8 V1.91 V (0.83%)17.3 W✓ OK (≤3%)
35 mm²125 A97 A0.83 V (0.36%)229.2 V1.36 V (0.59%)12.4 W✓ OK (≤3%)
50 mm²151 A118 A0.58 V (0.25%)229.4 V0.95 V (0.41%)8.7 W✓ OK (≤3%)
70 mm²192 A150 A0.41 V (0.18%)229.6 V0.68 V (0.3%)6.2 W✓ OK (≤3%)
95 mm²232 A181 A0.3 V (0.13%)229.7 V0.5 V (0.22%)4.6 W✓ OK (≤3%)
120 mm²269 A210 A0.24 V (0.1%)229.8 V0.4 V (0.17%)3.6 W✓ OK (≤3%)
150 mm²309 A241 A0.19 V (0.08%)229.8 V0.32 V (0.14%)2.9 W✓ OK (≤3%)
185 mm²353 A275 A0.16 V (0.07%)229.8 V0.26 V (0.11%)2.3 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.05%)229.9 V0.2 V (0.09%)1.8 W✓ OK (≤3%)
300 mm²477 A372 A0.1 V (0.04%)229.9 V0.16 V (0.07%)1.4 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.03%)229.9 V0.12 V (0.05%)1.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 15 Ampere ved 45 Meter (230V)

Hvilket kabeltværsnit kræves til 15A ved 45 meter (230V)?

Til 15 Ampere over 45 meter ved 230V anbefales 6 mm² kobberkabel (spændingsfald 4.82V / 2.09%).

Hvor mange kW svarer 15A ved 230V til?

Det svarer til 3.45 kW med en anbefalet sikring på 15A.