Kabeltværsnit for 80 Ampere ved 45 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 80 A over 45 m ved 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 6.16V (2.68%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 5.08V (2.21%)
Voltage at Load223.8 VLine Loss: 493.1 W
Max Power & Breaker18.4 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A102.72 V (44.66%)127.3 V169.44 V (73.67%)8217.6 WDrop High
2.5 mm²24 A18 A61.63 V (26.8%)168.4 V101.66 V (44.2%)4930.6 WDrop High
4 mm²32 A25 A38.52 V (16.75%)191.5 V63.54 V (27.63%)3081.6 WDrop High
6 mm²41 A32 A25.68 V (11.17%)204.3 V42.36 V (18.42%)2054.4 WDrop High
10 mm²57 A44 A15.41 V (6.7%)214.6 V25.42 V (11.05%)1232.6 WDrop High
16 mm²76 A59 A9.63 V (4.19%)220.4 V15.88 V (6.91%)770.4 WDrop High
25 mm²101 A78 A6.16 V (2.68%)223.8 V10.17 V (4.42%)493.1 W✓ OK (≤3%)
35 mm²125 A97 A4.4 V (1.91%)225.6 V7.26 V (3.16%)352.2 W✓ OK (≤3%)
50 mm²151 A118 A3.08 V (1.34%)226.9 V5.08 V (2.21%)246.5 W✓ OK (≤3%)
70 mm²192 A150 A2.2 V (0.96%)227.8 V3.63 V (1.58%)176.1 W✓ OK (≤3%)
95 mm²232 A181 A1.62 V (0.71%)228.4 V2.68 V (1.16%)129.8 W✓ OK (≤3%)
120 mm²269 A210 A1.28 V (0.56%)228.7 V2.12 V (0.92%)102.7 W✓ OK (≤3%)
150 mm²309 A241 A1.03 V (0.45%)229.0 V1.69 V (0.74%)82.2 W✓ OK (≤3%)
185 mm²353 A275 A0.83 V (0.36%)229.2 V1.37 V (0.6%)66.6 W✓ OK (≤3%)
240 mm²415 A324 A0.64 V (0.28%)229.4 V1.06 V (0.46%)51.4 W✓ OK (≤3%)
300 mm²477 A372 A0.51 V (0.22%)229.5 V0.85 V (0.37%)41.1 W✓ OK (≤3%)
400 mm²570 A445 A0.39 V (0.17%)229.6 V0.64 V (0.28%)30.8 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 80 Ampere ved 45 Meter (230V)

Hvilket kabeltværsnit kræves til 80A ved 45 meter (230V)?

Til 80 Ampere over 45 meter ved 230V anbefales 25 mm² kobberkabel (spændingsfald 6.16V / 2.68%).

Hvor mange kW svarer 80A ved 230V til?

Det svarer til 18.4 kW med en anbefalet sikring på 80A.