Kabeltværsnit for 160 Ampere ved 45 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 160 A over 45 m ved 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 4.4V (1.91%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 5.35V (2.33%)
Voltage at Load225.6 VLine Loss: 704.4 W
Max Power & Breaker36.8 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A205.44 V (89.32%)24.6 V338.88 V (147.34%)32870.4 WDrop High
2.5 mm²24 A18 A123.26 V (53.59%)106.7 V203.33 V (88.4%)19722.2 WDrop High
4 mm²32 A25 A77.04 V (33.5%)153.0 V127.08 V (55.25%)12326.4 WDrop High
6 mm²41 A32 A51.36 V (22.33%)178.6 V84.72 V (36.83%)8217.6 WDrop High
10 mm²57 A44 A30.82 V (13.4%)199.2 V50.83 V (22.1%)4930.6 WDrop High
16 mm²76 A59 A19.26 V (8.37%)210.7 V31.77 V (13.81%)3081.6 WDrop High
25 mm²101 A78 A12.33 V (5.36%)217.7 V20.33 V (8.84%)1972.2 WDrop High
35 mm²125 A97 A8.8 V (3.83%)221.2 V14.52 V (6.31%)1408.7 WDrop High
50 mm²151 A118 A6.16 V (2.68%)223.8 V10.17 V (4.42%)986.1 WDrop High
70 mm²192 A150 A4.4 V (1.91%)225.6 V7.26 V (3.16%)704.4 W✓ OK (≤3%)
95 mm²232 A181 A3.24 V (1.41%)226.8 V5.35 V (2.33%)519.0 W✓ OK (≤3%)
120 mm²269 A210 A2.57 V (1.12%)227.4 V4.24 V (1.84%)410.9 W✓ OK (≤3%)
150 mm²309 A241 A2.05 V (0.89%)227.9 V3.39 V (1.47%)328.7 W✓ OK (≤3%)
185 mm²353 A275 A1.67 V (0.72%)228.3 V2.75 V (1.19%)266.5 W✓ OK (≤3%)
240 mm²415 A324 A1.28 V (0.56%)228.7 V2.12 V (0.92%)205.4 W✓ OK (≤3%)
300 mm²477 A372 A1.03 V (0.45%)229.0 V1.69 V (0.74%)164.4 W✓ OK (≤3%)
400 mm²570 A445 A0.77 V (0.33%)229.2 V1.27 V (0.55%)123.3 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 160 Ampere ved 45 Meter (230V)

Hvilket kabeltværsnit kræves til 160A ved 45 meter (230V)?

Til 160 Ampere over 45 meter ved 230V anbefales 70 mm² kobberkabel (spændingsfald 4.4V / 1.91%).

Hvor mange kW svarer 160A ved 230V til?

Det svarer til 36.8 kW med en anbefalet sikring på 160A.