Kabeltværsnit for 150 Ampere ved 175 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 150 A over 175 m ved 230V.
Copper Cable (≤3% Drop)185 mm²Drop: 6.07V (2.64%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 6.18V (2.69%)
Voltage at Load223.9 VLine Loss: 910.9 W
Max Power & Breaker34.5 kW150A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 749.0 V (325.65%) | 0.0 V | 1235.5 V (537.17%) | 112350.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 449.4 V (195.39%) | 0.0 V | 741.3 V (322.3%) | 67410.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 280.88 V (122.12%) | 0.0 V | 463.31 V (201.44%) | 42131.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 187.25 V (81.41%) | 42.8 V | 308.88 V (134.29%) | 28087.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 112.35 V (48.85%) | 117.7 V | 185.32 V (80.58%) | 16852.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 70.22 V (30.53%) | 159.8 V | 115.83 V (50.36%) | 10532.8 W | Drop High |
| 25 mm² | 101 A | 78 A | 44.94 V (19.54%) | 185.1 V | 74.13 V (32.23%) | 6741.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 32.1 V (13.96%) | 197.9 V | 52.95 V (23.02%) | 4815.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 22.47 V (9.77%) | 207.5 V | 37.06 V (16.12%) | 3370.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 16.05 V (6.98%) | 213.9 V | 26.47 V (11.51%) | 2407.5 W | Drop High |
| 95 mm² | 232 A | 181 A | 11.83 V (5.14%) | 218.2 V | 19.51 V (8.48%) | 1773.9 W | Drop High |
| 120 mm² | 269 A | 210 A | 9.36 V (4.07%) | 220.6 V | 15.44 V (6.71%) | 1404.4 W | ~ ≤5% |
| 150 mm² | 309 A | 241 A | 7.49 V (3.26%) | 222.5 V | 12.35 V (5.37%) | 1123.5 W | ~ ≤5% |
| 185 mm² | 353 A | 275 A | 6.07 V (2.64%) | 223.9 V | 10.02 V (4.36%) | 910.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 4.68 V (2.04%) | 225.3 V | 7.72 V (3.36%) | 702.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 3.74 V (1.63%) | 226.3 V | 6.18 V (2.69%) | 561.8 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 2.81 V (1.22%) | 227.2 V | 4.63 V (2.01%) | 421.3 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 150 Ampere ved 175 Meter (230V)
Hvilket kabeltværsnit kræves til 150A ved 175 meter (230V)?
Til 150 Ampere over 175 meter ved 230V anbefales 185 mm² kobberkabel (spændingsfald 6.07V / 2.64%).
Hvor mange kW svarer 150A ved 230V til?
Det svarer til 34.5 kW med en anbefalet sikring på 150A.
Related Lengths & Currents (230V)
150A · 5m (230V)150A · 10m (230V)150A · 15m (230V)150A · 20m (230V)150A · 25m (230V)150A · 30m (230V)150A · 35m (230V)150A · 40m (230V)150A · 45m (230V)150A · 50m (230V)150A · 60m (230V)150A · 70m (230V)10A · 175m (230V)16A · 175m (230V)20A · 175m (230V)25A · 175m (230V)32A · 175m (230V)40A · 175m (230V)50A · 175m (230V)63A · 175m (230V)80A · 175m (230V)100A · 175m (230V)125A · 175m (230V)160A · 175m (230V)200A · 175m (230V)