Kabeltværsnit for 16 Ampere ved 600 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 16 A over 600 m ved 230V.
Copper Cable (≤3% Drop)70 mm²Drop: 5.87V (2.55%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 5.65V (2.46%)
Voltage at Load224.1 VLine Loss: 93.9 W
Max Power & Breaker3.68 kW16A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 600m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 273.92 V (119.1%) | 0.0 V | 451.84 V (196.45%) | 4382.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 164.35 V (71.46%) | 65.6 V | 271.1 V (117.87%) | 2629.6 W | Drop High |
| 4 mm² | 32 A | 25 A | 102.72 V (44.66%) | 127.3 V | 169.44 V (73.67%) | 1643.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 68.48 V (29.77%) | 161.5 V | 112.96 V (49.11%) | 1095.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 41.09 V (17.86%) | 188.9 V | 67.78 V (29.47%) | 657.4 W | Drop High |
| 16 mm² | 76 A | 59 A | 25.68 V (11.17%) | 204.3 V | 42.36 V (18.42%) | 410.9 W | Drop High |
| 25 mm² | 101 A | 78 A | 16.44 V (7.15%) | 213.6 V | 27.11 V (11.79%) | 263.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 11.74 V (5.1%) | 218.3 V | 19.36 V (8.42%) | 187.8 W | Drop High |
| 50 mm² | 151 A | 118 A | 8.22 V (3.57%) | 221.8 V | 13.56 V (5.89%) | 131.5 W | ~ ≤5% |
| 70 mm² | 192 A | 150 A | 5.87 V (2.55%) | 224.1 V | 9.68 V (4.21%) | 93.9 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 4.33 V (1.88%) | 225.7 V | 7.13 V (3.1%) | 69.2 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 3.42 V (1.49%) | 226.6 V | 5.65 V (2.46%) | 54.8 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 2.74 V (1.19%) | 227.3 V | 4.52 V (1.96%) | 43.8 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 2.22 V (0.97%) | 227.8 V | 3.66 V (1.59%) | 35.5 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 1.71 V (0.74%) | 228.3 V | 2.82 V (1.23%) | 27.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 1.37 V (0.6%) | 228.6 V | 2.26 V (0.98%) | 21.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.03 V (0.45%) | 229.0 V | 1.69 V (0.74%) | 16.4 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 16 Ampere ved 600 Meter (230V)
Hvilket kabeltværsnit kræves til 16A ved 600 meter (230V)?
Til 16 Ampere over 600 meter ved 230V anbefales 70 mm² kobberkabel (spændingsfald 5.87V / 2.55%).
Hvor mange kW svarer 16A ved 230V til?
Det svarer til 3.68 kW med en anbefalet sikring på 16A.
Related Lengths & Currents (230V)
16A · 5m (230V)16A · 10m (230V)16A · 15m (230V)16A · 20m (230V)16A · 25m (230V)16A · 30m (230V)16A · 35m (230V)16A · 40m (230V)16A · 45m (230V)16A · 50m (230V)16A · 60m (230V)16A · 70m (230V)10A · 600m (230V)20A · 600m (230V)25A · 600m (230V)32A · 600m (230V)40A · 600m (230V)50A · 600m (230V)63A · 600m (230V)80A · 600m (230V)100A · 600m (230V)125A · 600m (230V)160A · 600m (230V)200A · 600m (230V)