Kabeltværsnit for 80 Ampere ved 600 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 80 A over 600 m ved 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.47V (3.68%)
Voltage at Load223.2 VLine Loss: 547.8 W
Max Power & Breaker18.4 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1369.6 V (595.48%)0.0 V2259.2 V (982.26%)109568.0 WDrop High
2.5 mm²24 A18 A821.76 V (357.29%)0.0 V1355.52 V (589.36%)65740.8 WDrop High
4 mm²32 A25 A513.6 V (223.3%)0.0 V847.2 V (368.35%)41088.0 WDrop High
6 mm²41 A32 A342.4 V (148.87%)0.0 V564.8 V (245.57%)27392.0 WDrop High
10 mm²57 A44 A205.44 V (89.32%)24.6 V338.88 V (147.34%)16435.2 WDrop High
16 mm²76 A59 A128.4 V (55.83%)101.6 V211.8 V (92.09%)10272.0 WDrop High
25 mm²101 A78 A82.18 V (35.73%)147.8 V135.55 V (58.94%)6574.1 WDrop High
35 mm²125 A97 A58.7 V (25.52%)171.3 V96.82 V (42.1%)4695.8 WDrop High
50 mm²151 A118 A41.09 V (17.86%)188.9 V67.78 V (29.47%)3287.0 WDrop High
70 mm²192 A150 A29.35 V (12.76%)200.7 V48.41 V (21.05%)2347.9 WDrop High
95 mm²232 A181 A21.63 V (9.4%)208.4 V35.67 V (15.51%)1730.0 WDrop High
120 mm²269 A210 A17.12 V (7.44%)212.9 V28.24 V (12.28%)1369.6 WDrop High
150 mm²309 A241 A13.7 V (5.95%)216.3 V22.59 V (9.82%)1095.7 WDrop High
185 mm²353 A275 A11.1 V (4.83%)218.9 V18.32 V (7.96%)888.4 W~ ≤5%
240 mm²415 A324 A8.56 V (3.72%)221.4 V14.12 V (6.14%)684.8 W~ ≤5%
300 mm²477 A372 A6.85 V (2.98%)223.2 V11.3 V (4.91%)547.8 W✓ OK (≤3%)
400 mm²570 A445 A5.14 V (2.23%)224.9 V8.47 V (3.68%)410.9 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 80 Ampere ved 600 Meter (230V)

Hvilket kabeltværsnit kræves til 80A ved 600 meter (230V)?

Til 80 Ampere over 600 meter ved 230V anbefales 300 mm² kobberkabel (spændingsfald 6.85V / 2.98%).

Hvor mange kW svarer 80A ved 230V til?

Det svarer til 18.4 kW med en anbefalet sikring på 80A.