Kabeltværsnit for 200 Ampere ved 600 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 200 A over 600 m ved 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 21.18V (9.21%)
Voltage at Load223.6 VLine Loss: 1284.0 W
Max Power & Breaker46.0 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3424.0 V (1488.7%)0.0 V5648.0 V (2455.65%)684800.0 WDrop High
2.5 mm²24 A18 A2054.4 V (893.22%)0.0 V3388.8 V (1473.39%)410880.0 WDrop High
4 mm²32 A25 A1284.0 V (558.26%)0.0 V2118.0 V (920.87%)256800.0 WDrop High
6 mm²41 A32 A856.0 V (372.17%)0.0 V1412.0 V (613.91%)171200.0 WDrop High
10 mm²57 A44 A513.6 V (223.3%)0.0 V847.2 V (368.35%)102720.0 WDrop High
16 mm²76 A59 A321.0 V (139.57%)0.0 V529.5 V (230.22%)64200.0 WDrop High
25 mm²101 A78 A205.44 V (89.32%)24.6 V338.88 V (147.34%)41088.0 WDrop High
35 mm²125 A97 A146.74 V (63.8%)83.3 V242.06 V (105.24%)29348.6 WDrop High
50 mm²151 A118 A102.72 V (44.66%)127.3 V169.44 V (73.67%)20544.0 WDrop High
70 mm²192 A150 A73.37 V (31.9%)156.6 V121.03 V (52.62%)14674.3 WDrop High
95 mm²232 A181 A54.06 V (23.51%)175.9 V89.18 V (38.77%)10812.6 WDrop High
120 mm²269 A210 A42.8 V (18.61%)187.2 V70.6 V (30.7%)8560.0 WDrop High
150 mm²309 A241 A34.24 V (14.89%)195.8 V56.48 V (24.56%)6848.0 WDrop High
185 mm²353 A275 A27.76 V (12.07%)202.2 V45.79 V (19.91%)5552.4 WDrop High
240 mm²415 A324 A21.4 V (9.3%)208.6 V35.3 V (15.35%)4280.0 WDrop High
300 mm²477 A372 A17.12 V (7.44%)212.9 V28.24 V (12.28%)3424.0 WDrop High
400 mm²570 A445 A12.84 V (5.58%)217.2 V21.18 V (9.21%)2568.0 WDrop High

FAQ — Kabeltværsnit for 200 Ampere ved 600 Meter (230V)

Hvilket kabeltværsnit kræves til 200A ved 600 meter (230V)?

Til 200 Ampere over 600 meter ved 230V anbefales 2× 400 mm² kobberkabel (spændingsfald 6.42V / 2.79%).

Hvor mange kW svarer 200A ved 230V til?

Det svarer til 46.0 kW med en anbefalet sikring på 200A.