Kabeltværsnit for 160 Ampere ved 40 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 160 A over 40 m ved 400V.
Copper Cable (≤3% Drop)70 mm²Drop: 3.39V (0.85%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 4.12V (1.03%)
Voltage at Load396.6 VLine Loss: 939.2 W
Max Power & Breaker110.85 kW160A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 40m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 158.15 V (39.54%) | 241.9 V | 260.87 V (65.22%) | 43827.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 94.89 V (23.72%) | 305.1 V | 156.52 V (39.13%) | 26296.3 W | Drop High |
| 4 mm² | 32 A | 25 A | 59.31 V (14.83%) | 340.7 V | 97.83 V (24.46%) | 16435.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 39.54 V (9.88%) | 360.5 V | 65.22 V (16.3%) | 10956.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 23.72 V (5.93%) | 376.3 V | 39.13 V (9.78%) | 6574.1 W | Drop High |
| 16 mm² | 76 A | 59 A | 14.83 V (3.71%) | 385.2 V | 24.46 V (6.11%) | 4108.8 W | Drop High |
| 25 mm² | 101 A | 78 A | 9.49 V (2.37%) | 390.5 V | 15.65 V (3.91%) | 2629.6 W | Drop High |
| 35 mm² | 125 A | 97 A | 6.78 V (1.69%) | 393.2 V | 11.18 V (2.8%) | 1878.3 W | Drop High |
| 50 mm² | 151 A | 118 A | 4.74 V (1.19%) | 395.3 V | 7.83 V (1.96%) | 1314.8 W | Drop High |
| 70 mm² | 192 A | 150 A | 3.39 V (0.85%) | 396.6 V | 5.59 V (1.4%) | 939.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 2.5 V (0.62%) | 397.5 V | 4.12 V (1.03%) | 692.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.98 V (0.49%) | 398.0 V | 3.26 V (0.82%) | 547.8 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.58 V (0.4%) | 398.4 V | 2.61 V (0.65%) | 438.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.28 V (0.32%) | 398.7 V | 2.12 V (0.53%) | 355.4 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.99 V (0.25%) | 399.0 V | 1.63 V (0.41%) | 273.9 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.79 V (0.2%) | 399.2 V | 1.3 V (0.33%) | 219.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.59 V (0.15%) | 399.4 V | 0.98 V (0.24%) | 164.4 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 160 Ampere ved 40 Meter (400V)
Hvilket kabeltværsnit kræves til 160A ved 40 meter (400V)?
Til 160 Ampere over 40 meter ved 400V anbefales 70 mm² kobberkabel (spændingsfald 3.39V / 0.85%).
Hvor mange kW svarer 160A ved 400V til?
Det svarer til 110.85 kW med en anbefalet sikring på 160A.
Related Lengths & Currents (400V)
160A · 5m (400V)160A · 10m (400V)160A · 15m (400V)160A · 20m (400V)160A · 25m (400V)160A · 30m (400V)160A · 35m (400V)160A · 45m (400V)160A · 50m (400V)160A · 60m (400V)160A · 70m (400V)10A · 40m (400V)16A · 40m (400V)20A · 40m (400V)25A · 40m (400V)32A · 40m (400V)40A · 40m (400V)50A · 40m (400V)63A · 40m (400V)80A · 40m (400V)100A · 40m (400V)125A · 40m (400V)200A · 40m (400V)