Kabeltværsnit for 16 Ampere ved 40 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 16 A over 40 m ved 400V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 9.49V (2.37%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 9.78V (2.45%)
Voltage at Load390.5 VLine Loss: 263.0 W
Max Power & Breaker11.09 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A15.81 V (3.95%)384.2 V26.09 V (6.52%)438.3 W~ ≤5%
2.5 mm²24 A18 A9.49 V (2.37%)390.5 V15.65 V (3.91%)263.0 W✓ OK (≤3%)
4 mm²32 A25 A5.93 V (1.48%)394.1 V9.78 V (2.45%)164.4 W✓ OK (≤3%)
6 mm²41 A32 A3.95 V (0.99%)396.0 V6.52 V (1.63%)109.6 W✓ OK (≤3%)
10 mm²57 A44 A2.37 V (0.59%)397.6 V3.91 V (0.98%)65.7 W✓ OK (≤3%)
16 mm²76 A59 A1.48 V (0.37%)398.5 V2.45 V (0.61%)41.1 W✓ OK (≤3%)
25 mm²101 A78 A0.95 V (0.24%)399.1 V1.57 V (0.39%)26.3 W✓ OK (≤3%)
35 mm²125 A97 A0.68 V (0.17%)399.3 V1.12 V (0.28%)18.8 W✓ OK (≤3%)
50 mm²151 A118 A0.47 V (0.12%)399.5 V0.78 V (0.2%)13.1 W✓ OK (≤3%)
70 mm²192 A150 A0.34 V (0.08%)399.7 V0.56 V (0.14%)9.4 W✓ OK (≤3%)
95 mm²232 A181 A0.25 V (0.06%)399.8 V0.41 V (0.1%)6.9 W✓ OK (≤3%)
120 mm²269 A210 A0.2 V (0.05%)399.8 V0.33 V (0.08%)5.5 W✓ OK (≤3%)
150 mm²309 A241 A0.16 V (0.04%)399.8 V0.26 V (0.07%)4.4 W✓ OK (≤3%)
185 mm²353 A275 A0.13 V (0.03%)399.9 V0.21 V (0.05%)3.6 W✓ OK (≤3%)
240 mm²415 A324 A0.1 V (0.02%)399.9 V0.16 V (0.04%)2.7 W✓ OK (≤3%)
300 mm²477 A372 A0.08 V (0.02%)399.9 V0.13 V (0.03%)2.2 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.01%)399.9 V0.1 V (0.02%)1.6 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 16 Ampere ved 40 Meter (400V)

Hvilket kabeltværsnit kræves til 16A ved 40 meter (400V)?

Til 16 Ampere over 40 meter ved 400V anbefales 2.5 mm² kobberkabel (spændingsfald 9.49V / 2.37%).

Hvor mange kW svarer 16A ved 400V til?

Det svarer til 11.09 kW med en anbefalet sikring på 16A.