Kabeltværsnit for 160 Ampere ved 70 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 160 A over 70 m ved 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 5.93V (1.48%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 7.21V (1.8%)
Voltage at Load394.1 VLine Loss: 1643.5 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A276.76 V (69.19%)123.2 V456.52 V (114.13%)76697.6 WDrop High
2.5 mm²24 A18 A166.06 V (41.51%)233.9 V273.91 V (68.48%)46018.6 WDrop High
4 mm²32 A25 A103.78 V (25.95%)296.2 V171.2 V (42.8%)28761.6 WDrop High
6 mm²41 A32 A69.19 V (17.3%)330.8 V114.13 V (28.53%)19174.4 WDrop High
10 mm²57 A44 A41.51 V (10.38%)358.5 V68.48 V (17.12%)11504.6 WDrop High
16 mm²76 A59 A25.95 V (6.49%)374.1 V42.8 V (10.7%)7190.4 WDrop High
25 mm²101 A78 A16.61 V (4.15%)383.4 V27.39 V (6.85%)4601.9 WDrop High
35 mm²125 A97 A11.86 V (2.97%)388.1 V19.57 V (4.89%)3287.0 WDrop High
50 mm²151 A118 A8.3 V (2.08%)391.7 V13.7 V (3.42%)2300.9 WDrop High
70 mm²192 A150 A5.93 V (1.48%)394.1 V9.78 V (2.45%)1643.5 W✓ OK (≤3%)
95 mm²232 A181 A4.37 V (1.09%)395.6 V7.21 V (1.8%)1211.0 W✓ OK (≤3%)
120 mm²269 A210 A3.46 V (0.86%)396.5 V5.71 V (1.43%)958.7 W✓ OK (≤3%)
150 mm²309 A241 A2.77 V (0.69%)397.2 V4.57 V (1.14%)767.0 W✓ OK (≤3%)
185 mm²353 A275 A2.24 V (0.56%)397.8 V3.7 V (0.93%)621.9 W✓ OK (≤3%)
240 mm²415 A324 A1.73 V (0.43%)398.3 V2.85 V (0.71%)479.4 W✓ OK (≤3%)
300 mm²477 A372 A1.38 V (0.35%)398.6 V2.28 V (0.57%)383.5 W✓ OK (≤3%)
400 mm²570 A445 A1.04 V (0.26%)399.0 V1.71 V (0.43%)287.6 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 160 Ampere ved 70 Meter (400V)

Hvilket kabeltværsnit kræves til 160A ved 70 meter (400V)?

Til 160 Ampere over 70 meter ved 400V anbefales 70 mm² kobberkabel (spændingsfald 5.93V / 1.48%).

Hvor mange kW svarer 160A ved 400V til?

Det svarer til 110.85 kW med en anbefalet sikring på 160A.