Kabeltværsnit for 225 Ampere ved 30 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 225 A over 30 m ved 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 3.04V (1.32%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 3.18V (1.38%)
Voltage at Load227.0 VLine Loss: 684.2 W
Max Power & Breaker51.75 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A192.6 V (83.74%)37.4 V317.7 V (138.13%)43335.0 WDrop High
2.5 mm²24 A18 A115.56 V (50.24%)114.4 V190.62 V (82.88%)26001.0 WDrop High
4 mm²32 A25 A72.23 V (31.4%)157.8 V119.14 V (51.8%)16250.6 WDrop High
6 mm²41 A32 A48.15 V (20.93%)181.8 V79.42 V (34.53%)10833.8 WDrop High
10 mm²57 A44 A28.89 V (12.56%)201.1 V47.65 V (20.72%)6500.3 WDrop High
16 mm²76 A59 A18.06 V (7.85%)211.9 V29.78 V (12.95%)4062.7 WDrop High
25 mm²101 A78 A11.56 V (5.02%)218.4 V19.06 V (8.29%)2600.1 WDrop High
35 mm²125 A97 A8.25 V (3.59%)221.7 V13.62 V (5.92%)1857.2 WDrop High
50 mm²151 A118 A5.78 V (2.51%)224.2 V9.53 V (4.14%)1300.1 WDrop High
70 mm²192 A150 A4.13 V (1.79%)225.9 V6.81 V (2.96%)928.6 WDrop High
95 mm²232 A181 A3.04 V (1.32%)227.0 V5.02 V (2.18%)684.2 W✓ OK (≤3%)
120 mm²269 A210 A2.41 V (1.05%)227.6 V3.97 V (1.73%)541.7 W✓ OK (≤3%)
150 mm²309 A241 A1.93 V (0.84%)228.1 V3.18 V (1.38%)433.4 W✓ OK (≤3%)
185 mm²353 A275 A1.56 V (0.68%)228.4 V2.58 V (1.12%)351.4 W✓ OK (≤3%)
240 mm²415 A324 A1.2 V (0.52%)228.8 V1.99 V (0.86%)270.8 W✓ OK (≤3%)
300 mm²477 A372 A0.96 V (0.42%)229.0 V1.59 V (0.69%)216.7 W✓ OK (≤3%)
400 mm²570 A445 A0.72 V (0.31%)229.3 V1.19 V (0.52%)162.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 225 Ampere ved 30 Meter (230V)

Hvilket kabeltværsnit kræves til 225A ved 30 meter (230V)?

Til 225 Ampere over 30 meter ved 230V anbefales 95 mm² kobberkabel (spændingsfald 3.04V / 1.32%).

Hvor mange kW svarer 225A ved 230V til?

Det svarer til 51.75 kW med en anbefalet sikring på 225A.