Kabeltværsnit for 225 Ampere ved 20 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 225 A over 20 m ved 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 2.03V (0.88%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 2.12V (0.92%)
Voltage at Load228.0 VLine Loss: 456.2 W
Max Power & Breaker51.75 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A128.4 V (55.83%)101.6 V211.8 V (92.09%)28890.0 WDrop High
2.5 mm²24 A18 A77.04 V (33.5%)153.0 V127.08 V (55.25%)17334.0 WDrop High
4 mm²32 A25 A48.15 V (20.93%)181.8 V79.42 V (34.53%)10833.8 WDrop High
6 mm²41 A32 A32.1 V (13.96%)197.9 V52.95 V (23.02%)7222.5 WDrop High
10 mm²57 A44 A19.26 V (8.37%)210.7 V31.77 V (13.81%)4333.5 WDrop High
16 mm²76 A59 A12.04 V (5.23%)218.0 V19.86 V (8.63%)2708.4 WDrop High
25 mm²101 A78 A7.7 V (3.35%)222.3 V12.71 V (5.53%)1733.4 WDrop High
35 mm²125 A97 A5.5 V (2.39%)224.5 V9.08 V (3.95%)1238.1 WDrop High
50 mm²151 A118 A3.85 V (1.67%)226.1 V6.35 V (2.76%)866.7 WDrop High
70 mm²192 A150 A2.75 V (1.2%)227.2 V4.54 V (1.97%)619.1 WDrop High
95 mm²232 A181 A2.03 V (0.88%)228.0 V3.34 V (1.45%)456.2 W✓ OK (≤3%)
120 mm²269 A210 A1.6 V (0.7%)228.4 V2.65 V (1.15%)361.1 W✓ OK (≤3%)
150 mm²309 A241 A1.28 V (0.56%)228.7 V2.12 V (0.92%)288.9 W✓ OK (≤3%)
185 mm²353 A275 A1.04 V (0.45%)229.0 V1.72 V (0.75%)234.2 W✓ OK (≤3%)
240 mm²415 A324 A0.8 V (0.35%)229.2 V1.32 V (0.58%)180.6 W✓ OK (≤3%)
300 mm²477 A372 A0.64 V (0.28%)229.4 V1.06 V (0.46%)144.4 W✓ OK (≤3%)
400 mm²570 A445 A0.48 V (0.21%)229.5 V0.79 V (0.35%)108.3 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 225 Ampere ved 20 Meter (230V)

Hvilket kabeltværsnit kræves til 225A ved 20 meter (230V)?

Til 225 Ampere over 20 meter ved 230V anbefales 95 mm² kobberkabel (spændingsfald 2.03V / 0.88%).

Hvor mange kW svarer 225A ved 230V til?

Det svarer til 51.75 kW med en anbefalet sikring på 225A.