Kabeltværsnit for 30 Ampere ved 600 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 30 A over 600 m ved 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 9.53V (2.38%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 11.58V (2.9%)
Voltage at Load390.5 VLine Loss: 495.3 W
Max Power & Breaker20.78 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A444.79 V (111.2%)0.0 V733.7 V (183.42%)23112.0 WDrop High
2.5 mm²24 A18 A266.87 V (66.72%)133.1 V440.22 V (110.05%)13867.2 WDrop High
4 mm²32 A25 A166.8 V (41.7%)233.2 V275.14 V (68.78%)8667.0 WDrop High
6 mm²41 A32 A111.2 V (27.8%)288.8 V183.42 V (45.86%)5778.0 WDrop High
10 mm²57 A44 A66.72 V (16.68%)333.3 V110.05 V (27.51%)3466.8 WDrop High
16 mm²76 A59 A41.7 V (10.42%)358.3 V68.78 V (17.2%)2166.8 WDrop High
25 mm²101 A78 A26.69 V (6.67%)373.3 V44.02 V (11.01%)1386.7 WDrop High
35 mm²125 A97 A19.06 V (4.77%)380.9 V31.44 V (7.86%)990.5 W~ ≤5%
50 mm²151 A118 A13.34 V (3.34%)386.7 V22.01 V (5.5%)693.4 W~ ≤5%
70 mm²192 A150 A9.53 V (2.38%)390.5 V15.72 V (3.93%)495.3 W✓ OK (≤3%)
95 mm²232 A181 A7.02 V (1.76%)393.0 V11.58 V (2.9%)364.9 W✓ OK (≤3%)
120 mm²269 A210 A5.56 V (1.39%)394.4 V9.17 V (2.29%)288.9 W✓ OK (≤3%)
150 mm²309 A241 A4.45 V (1.11%)395.6 V7.34 V (1.83%)231.1 W✓ OK (≤3%)
185 mm²353 A275 A3.61 V (0.9%)396.4 V5.95 V (1.49%)187.4 W✓ OK (≤3%)
240 mm²415 A324 A2.78 V (0.69%)397.2 V4.59 V (1.15%)144.4 W✓ OK (≤3%)
300 mm²477 A372 A2.22 V (0.56%)397.8 V3.67 V (0.92%)115.6 W✓ OK (≤3%)
400 mm²570 A445 A1.67 V (0.42%)398.3 V2.75 V (0.69%)86.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 30 Ampere ved 600 Meter (400V)

Hvilket kabeltværsnit kræves til 30A ved 600 meter (400V)?

Til 30 Ampere over 600 meter ved 400V anbefales 70 mm² kobberkabel (spændingsfald 9.53V / 2.38%).

Hvor mange kW svarer 30A ved 400V til?

Det svarer til 20.78 kW med en anbefalet sikring på 30A.