⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 300 Ampere ved 90 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 300 A over 90 m ved 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 6.67V (1.67%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 6.88V (1.72%)
Voltage at Load393.3 VLine Loss: 3466.8 W
Max Power & Breaker207.85 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A667.19 V (166.8%)0.0 V1100.55 V (275.14%)346680.0 WDrop High
2.5 mm²24 A18 A400.31 V (100.08%)0.0 V660.33 V (165.08%)208008.0 WDrop High
4 mm²32 A25 A250.19 V (62.55%)149.8 V412.7 V (103.18%)130005.0 WDrop High
6 mm²41 A32 A166.8 V (41.7%)233.2 V275.14 V (68.78%)86670.0 WDrop High
10 mm²57 A44 A100.08 V (25.02%)299.9 V165.08 V (41.27%)52002.0 WDrop High
16 mm²76 A59 A62.55 V (15.64%)337.5 V103.18 V (25.79%)32501.2 WDrop High
25 mm²101 A78 A40.03 V (10.01%)360.0 V66.03 V (16.51%)20800.8 WDrop High
35 mm²125 A97 A28.59 V (7.15%)371.4 V47.17 V (11.79%)14857.7 WDrop High
50 mm²151 A118 A20.02 V (5.0%)380.0 V33.02 V (8.25%)10400.4 WDrop High
70 mm²192 A150 A14.3 V (3.57%)385.7 V23.58 V (5.9%)7428.9 WDrop High
95 mm²232 A181 A10.53 V (2.63%)389.5 V17.38 V (4.34%)5473.9 WDrop High
120 mm²269 A210 A8.34 V (2.08%)391.7 V13.76 V (3.44%)4333.5 WDrop High
150 mm²309 A241 A6.67 V (1.67%)393.3 V11.01 V (2.75%)3466.8 W✓ OK (≤3%)
185 mm²353 A275 A5.41 V (1.35%)394.6 V8.92 V (2.23%)2810.9 W✓ OK (≤3%)
240 mm²415 A324 A4.17 V (1.04%)395.8 V6.88 V (1.72%)2166.7 W✓ OK (≤3%)
300 mm²477 A372 A3.34 V (0.83%)396.7 V5.5 V (1.38%)1733.4 W✓ OK (≤3%)
400 mm²570 A445 A2.5 V (0.63%)397.5 V4.13 V (1.03%)1300.0 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 300 Ampere ved 90 Meter (400V)

Hvilket kabeltværsnit kræves til 300A ved 90 meter (400V)?

Til 300 Ampere over 90 meter ved 400V anbefales 150 mm² kobberkabel (spændingsfald 6.67V / 1.67%).

Hvor mange kW svarer 300A ved 400V til?

Det svarer til 207.85 kW med en anbefalet sikring på 300A.