Kabeltværsnit for 35 Ampere ved 45 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 35 A over 45 m ved 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 9.73V (2.43%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 9.63V (2.41%)
Voltage at Load390.3 VLine Loss: 589.8 W
Max Power & Breaker24.25 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A38.92 V (9.73%)361.1 V64.2 V (16.05%)2359.3 WDrop High
2.5 mm²24 A18 A23.35 V (5.84%)376.6 V38.52 V (9.63%)1415.6 WDrop High
4 mm²32 A25 A14.59 V (3.65%)385.4 V24.07 V (6.02%)884.8 WDrop High
6 mm²41 A32 A9.73 V (2.43%)390.3 V16.05 V (4.01%)589.8 W✓ OK (≤3%)
10 mm²57 A44 A5.84 V (1.46%)394.2 V9.63 V (2.41%)353.9 W✓ OK (≤3%)
16 mm²76 A59 A3.65 V (0.91%)396.4 V6.02 V (1.5%)221.2 W✓ OK (≤3%)
25 mm²101 A78 A2.34 V (0.58%)397.7 V3.85 V (0.96%)141.6 W✓ OK (≤3%)
35 mm²125 A97 A1.67 V (0.42%)398.3 V2.75 V (0.69%)101.1 W✓ OK (≤3%)
50 mm²151 A118 A1.17 V (0.29%)398.8 V1.93 V (0.48%)70.8 W✓ OK (≤3%)
70 mm²192 A150 A0.83 V (0.21%)399.2 V1.38 V (0.34%)50.6 W✓ OK (≤3%)
95 mm²232 A181 A0.61 V (0.15%)399.4 V1.01 V (0.25%)37.3 W✓ OK (≤3%)
120 mm²269 A210 A0.49 V (0.12%)399.5 V0.8 V (0.2%)29.5 W✓ OK (≤3%)
150 mm²309 A241 A0.39 V (0.1%)399.6 V0.64 V (0.16%)23.6 W✓ OK (≤3%)
185 mm²353 A275 A0.32 V (0.08%)399.7 V0.52 V (0.13%)19.1 W✓ OK (≤3%)
240 mm²415 A324 A0.24 V (0.06%)399.8 V0.4 V (0.1%)14.7 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.05%)399.8 V0.32 V (0.08%)11.8 W✓ OK (≤3%)
400 mm²570 A445 A0.15 V (0.04%)399.9 V0.24 V (0.06%)8.8 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 35 Ampere ved 45 Meter (400V)

Hvilket kabeltværsnit kræves til 35A ved 45 meter (400V)?

Til 35 Ampere over 45 meter ved 400V anbefales 6 mm² kobberkabel (spændingsfald 9.73V / 2.43%).

Hvor mange kW svarer 35A ved 400V til?

Det svarer til 24.25 kW med en anbefalet sikring på 35A.