Kabeltværsnit for 35 Ampere ved 15 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 35 A over 15 m ved 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 3.24V (0.81%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 3.21V (0.8%)
Voltage at Load396.8 VLine Loss: 196.6 W
Max Power & Breaker24.25 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A12.97 V (3.24%)387.0 V21.4 V (5.35%)786.4 WDrop High
2.5 mm²24 A18 A7.78 V (1.95%)392.2 V12.84 V (3.21%)471.9 WDrop High
4 mm²32 A25 A4.86 V (1.22%)395.1 V8.02 V (2.01%)294.9 WDrop High
6 mm²41 A32 A3.24 V (0.81%)396.8 V5.35 V (1.34%)196.6 W✓ OK (≤3%)
10 mm²57 A44 A1.95 V (0.49%)398.1 V3.21 V (0.8%)118.0 W✓ OK (≤3%)
16 mm²76 A59 A1.22 V (0.3%)398.8 V2.01 V (0.5%)73.7 W✓ OK (≤3%)
25 mm²101 A78 A0.78 V (0.19%)399.2 V1.28 V (0.32%)47.2 W✓ OK (≤3%)
35 mm²125 A97 A0.56 V (0.14%)399.4 V0.92 V (0.23%)33.7 W✓ OK (≤3%)
50 mm²151 A118 A0.39 V (0.1%)399.6 V0.64 V (0.16%)23.6 W✓ OK (≤3%)
70 mm²192 A150 A0.28 V (0.07%)399.7 V0.46 V (0.11%)16.9 W✓ OK (≤3%)
95 mm²232 A181 A0.2 V (0.05%)399.8 V0.34 V (0.08%)12.4 W✓ OK (≤3%)
120 mm²269 A210 A0.16 V (0.04%)399.8 V0.27 V (0.07%)9.8 W✓ OK (≤3%)
150 mm²309 A241 A0.13 V (0.03%)399.9 V0.21 V (0.05%)7.9 W✓ OK (≤3%)
185 mm²353 A275 A0.11 V (0.03%)399.9 V0.17 V (0.04%)6.4 W✓ OK (≤3%)
240 mm²415 A324 A0.08 V (0.02%)399.9 V0.13 V (0.03%)4.9 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.02%)399.9 V0.11 V (0.03%)3.9 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.01%)400.0 V0.08 V (0.02%)2.9 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 35 Ampere ved 15 Meter (400V)

Hvilket kabeltværsnit kræves til 35A ved 15 meter (400V)?

Til 35 Ampere over 15 meter ved 400V anbefales 6 mm² kobberkabel (spændingsfald 3.24V / 0.81%).

Hvor mange kW svarer 35A ved 400V til?

Det svarer til 24.25 kW med en anbefalet sikring på 35A.