Kabeltværsnit for 35 Ampere ved 35 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 35 A over 35 m ved 400V.
Copper Cable (≤3% Drop)6 mm²Drop: 7.57V (1.89%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 7.49V (1.87%)
Voltage at Load392.4 VLine Loss: 458.8 W
Max Power & Breaker24.25 kW35A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 30.27 V (7.57%) | 369.7 V | 49.93 V (12.48%) | 1835.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 18.16 V (4.54%) | 381.8 V | 29.96 V (7.49%) | 1101.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 11.35 V (2.84%) | 388.6 V | 18.72 V (4.68%) | 688.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 7.57 V (1.89%) | 392.4 V | 12.48 V (3.12%) | 458.8 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 4.54 V (1.14%) | 395.5 V | 7.49 V (1.87%) | 275.3 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 2.84 V (0.71%) | 397.2 V | 4.68 V (1.17%) | 172.0 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 1.82 V (0.45%) | 398.2 V | 3.0 V (0.75%) | 110.1 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 1.3 V (0.32%) | 398.7 V | 2.14 V (0.53%) | 78.6 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.91 V (0.23%) | 399.1 V | 1.5 V (0.37%) | 55.1 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.65 V (0.16%) | 399.4 V | 1.07 V (0.27%) | 39.3 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.48 V (0.12%) | 399.5 V | 0.79 V (0.2%) | 29.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.38 V (0.09%) | 399.6 V | 0.62 V (0.16%) | 22.9 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.3 V (0.08%) | 399.7 V | 0.5 V (0.12%) | 18.4 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.25 V (0.06%) | 399.8 V | 0.4 V (0.1%) | 14.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.19 V (0.05%) | 399.8 V | 0.31 V (0.08%) | 11.5 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.15 V (0.04%) | 399.8 V | 0.25 V (0.06%) | 9.2 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.11 V (0.03%) | 399.9 V | 0.19 V (0.05%) | 6.9 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 35 Ampere ved 35 Meter (400V)
Hvilket kabeltværsnit kræves til 35A ved 35 meter (400V)?
Til 35 Ampere over 35 meter ved 400V anbefales 6 mm² kobberkabel (spændingsfald 7.57V / 1.89%).
Hvor mange kW svarer 35A ved 400V til?
Det svarer til 24.25 kW med en anbefalet sikring på 35A.
Related Lengths & Currents (400V)
35A · 5m (400V)35A · 10m (400V)35A · 15m (400V)35A · 20m (400V)35A · 25m (400V)35A · 30m (400V)35A · 40m (400V)35A · 45m (400V)35A · 50m (400V)35A · 60m (400V)35A · 70m (400V)10A · 35m (400V)16A · 35m (400V)20A · 35m (400V)25A · 35m (400V)32A · 35m (400V)40A · 35m (400V)50A · 35m (400V)63A · 35m (400V)80A · 35m (400V)100A · 35m (400V)125A · 35m (400V)160A · 35m (400V)200A · 35m (400V)