Kabeltværsnit for 35 Ampere ved 35 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 35 A over 35 m ved 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 7.57V (1.89%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 7.49V (1.87%)
Voltage at Load392.4 VLine Loss: 458.8 W
Max Power & Breaker24.25 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A30.27 V (7.57%)369.7 V49.93 V (12.48%)1835.0 WDrop High
2.5 mm²24 A18 A18.16 V (4.54%)381.8 V29.96 V (7.49%)1101.0 WDrop High
4 mm²32 A25 A11.35 V (2.84%)388.6 V18.72 V (4.68%)688.1 WDrop High
6 mm²41 A32 A7.57 V (1.89%)392.4 V12.48 V (3.12%)458.8 W✓ OK (≤3%)
10 mm²57 A44 A4.54 V (1.14%)395.5 V7.49 V (1.87%)275.3 W✓ OK (≤3%)
16 mm²76 A59 A2.84 V (0.71%)397.2 V4.68 V (1.17%)172.0 W✓ OK (≤3%)
25 mm²101 A78 A1.82 V (0.45%)398.2 V3.0 V (0.75%)110.1 W✓ OK (≤3%)
35 mm²125 A97 A1.3 V (0.32%)398.7 V2.14 V (0.53%)78.6 W✓ OK (≤3%)
50 mm²151 A118 A0.91 V (0.23%)399.1 V1.5 V (0.37%)55.1 W✓ OK (≤3%)
70 mm²192 A150 A0.65 V (0.16%)399.4 V1.07 V (0.27%)39.3 W✓ OK (≤3%)
95 mm²232 A181 A0.48 V (0.12%)399.5 V0.79 V (0.2%)29.0 W✓ OK (≤3%)
120 mm²269 A210 A0.38 V (0.09%)399.6 V0.62 V (0.16%)22.9 W✓ OK (≤3%)
150 mm²309 A241 A0.3 V (0.08%)399.7 V0.5 V (0.12%)18.4 W✓ OK (≤3%)
185 mm²353 A275 A0.25 V (0.06%)399.8 V0.4 V (0.1%)14.9 W✓ OK (≤3%)
240 mm²415 A324 A0.19 V (0.05%)399.8 V0.31 V (0.08%)11.5 W✓ OK (≤3%)
300 mm²477 A372 A0.15 V (0.04%)399.8 V0.25 V (0.06%)9.2 W✓ OK (≤3%)
400 mm²570 A445 A0.11 V (0.03%)399.9 V0.19 V (0.05%)6.9 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 35 Ampere ved 35 Meter (400V)

Hvilket kabeltværsnit kræves til 35A ved 35 meter (400V)?

Til 35 Ampere over 35 meter ved 400V anbefales 6 mm² kobberkabel (spændingsfald 7.57V / 1.89%).

Hvor mange kW svarer 35A ved 400V til?

Det svarer til 24.25 kW med en anbefalet sikring på 35A.