Kabeltværsnit for 35 Ampere ved 5 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 35 A over 5 m ved 230V.

Copper Cable (≤3% Drop)6 mm²Drop: 1.25V (0.54%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 1.24V (0.54%)
Voltage at Load228.8 VLine Loss: 43.7 W
Max Power & Breaker8.05 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4.99 V (2.17%)225.0 V8.24 V (3.58%)174.8 WDrop High
2.5 mm²24 A18 A3.0 V (1.3%)227.0 V4.94 V (2.15%)104.9 WDrop High
4 mm²32 A25 A1.87 V (0.81%)228.1 V3.09 V (1.34%)65.5 WDrop High
6 mm²41 A32 A1.25 V (0.54%)228.8 V2.06 V (0.9%)43.7 W✓ OK (≤3%)
10 mm²57 A44 A0.75 V (0.33%)229.3 V1.24 V (0.54%)26.2 W✓ OK (≤3%)
16 mm²76 A59 A0.47 V (0.2%)229.5 V0.77 V (0.34%)16.4 W✓ OK (≤3%)
25 mm²101 A78 A0.3 V (0.13%)229.7 V0.49 V (0.21%)10.5 W✓ OK (≤3%)
35 mm²125 A97 A0.21 V (0.09%)229.8 V0.35 V (0.15%)7.5 W✓ OK (≤3%)
50 mm²151 A118 A0.15 V (0.07%)229.9 V0.25 V (0.11%)5.2 W✓ OK (≤3%)
70 mm²192 A150 A0.11 V (0.05%)229.9 V0.18 V (0.08%)3.7 W✓ OK (≤3%)
95 mm²232 A181 A0.08 V (0.03%)229.9 V0.13 V (0.06%)2.8 W✓ OK (≤3%)
120 mm²269 A210 A0.06 V (0.03%)229.9 V0.1 V (0.04%)2.2 W✓ OK (≤3%)
150 mm²309 A241 A0.05 V (0.02%)230.0 V0.08 V (0.04%)1.7 W✓ OK (≤3%)
185 mm²353 A275 A0.04 V (0.02%)230.0 V0.07 V (0.03%)1.4 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.01%)230.0 V0.05 V (0.02%)1.1 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.01%)230.0 V0.04 V (0.02%)0.9 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.01%)230.0 V0.03 V (0.01%)0.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 35 Ampere ved 5 Meter (230V)

Hvilket kabeltværsnit kræves til 35A ved 5 meter (230V)?

Til 35 Ampere over 5 meter ved 230V anbefales 6 mm² kobberkabel (spændingsfald 1.25V / 0.54%).

Hvor mange kW svarer 35A ved 230V til?

Det svarer til 8.05 kW med en anbefalet sikring på 35A.