Kabeltværsnit for 35 Ampere ved 25 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 35 A over 25 m ved 230V.

Copper Cable (≤3% Drop)6 mm²Drop: 6.24V (2.71%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 6.18V (2.69%)
Voltage at Load223.8 VLine Loss: 218.5 W
Max Power & Breaker8.05 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A24.97 V (10.86%)205.0 V41.18 V (17.91%)873.8 WDrop High
2.5 mm²24 A18 A14.98 V (6.51%)215.0 V24.71 V (10.74%)524.3 WDrop High
4 mm²32 A25 A9.36 V (4.07%)220.6 V15.44 V (6.71%)327.7 WDrop High
6 mm²41 A32 A6.24 V (2.71%)223.8 V10.3 V (4.48%)218.5 W✓ OK (≤3%)
10 mm²57 A44 A3.74 V (1.63%)226.3 V6.18 V (2.69%)131.1 W✓ OK (≤3%)
16 mm²76 A59 A2.34 V (1.02%)227.7 V3.86 V (1.68%)81.9 W✓ OK (≤3%)
25 mm²101 A78 A1.5 V (0.65%)228.5 V2.47 V (1.07%)52.4 W✓ OK (≤3%)
35 mm²125 A97 A1.07 V (0.47%)228.9 V1.76 V (0.77%)37.4 W✓ OK (≤3%)
50 mm²151 A118 A0.75 V (0.33%)229.3 V1.24 V (0.54%)26.2 W✓ OK (≤3%)
70 mm²192 A150 A0.53 V (0.23%)229.5 V0.88 V (0.38%)18.7 W✓ OK (≤3%)
95 mm²232 A181 A0.39 V (0.17%)229.6 V0.65 V (0.28%)13.8 W✓ OK (≤3%)
120 mm²269 A210 A0.31 V (0.14%)229.7 V0.51 V (0.22%)10.9 W✓ OK (≤3%)
150 mm²309 A241 A0.25 V (0.11%)229.8 V0.41 V (0.18%)8.7 W✓ OK (≤3%)
185 mm²353 A275 A0.2 V (0.09%)229.8 V0.33 V (0.15%)7.1 W✓ OK (≤3%)
240 mm²415 A324 A0.16 V (0.07%)229.8 V0.26 V (0.11%)5.5 W✓ OK (≤3%)
300 mm²477 A372 A0.12 V (0.05%)229.9 V0.21 V (0.09%)4.4 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.04%)229.9 V0.15 V (0.07%)3.3 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 35 Ampere ved 25 Meter (230V)

Hvilket kabeltværsnit kræves til 35A ved 25 meter (230V)?

Til 35 Ampere over 25 meter ved 230V anbefales 6 mm² kobberkabel (spændingsfald 6.24V / 2.71%).

Hvor mange kW svarer 35A ved 230V til?

Det svarer til 8.05 kW med en anbefalet sikring på 35A.