Kabeltværsnit for 35 Ampere ved 50 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 35 A over 50 m ved 230V.
Copper Cable (≤3% Drop)16 mm²Drop: 4.68V (2.04%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 4.94V (2.15%)
Voltage at Load225.3 VLine Loss: 163.8 W
Max Power & Breaker8.05 kW35A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 50m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 49.93 V (21.71%) | 180.1 V | 82.37 V (35.81%) | 1747.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 29.96 V (13.03%) | 200.0 V | 49.42 V (21.49%) | 1048.6 W | Drop High |
| 4 mm² | 32 A | 25 A | 18.72 V (8.14%) | 211.3 V | 30.89 V (13.43%) | 655.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 12.48 V (5.43%) | 217.5 V | 20.59 V (8.95%) | 436.9 W | Drop High |
| 10 mm² | 57 A | 44 A | 7.49 V (3.26%) | 222.5 V | 12.35 V (5.37%) | 262.1 W | ~ ≤5% |
| 16 mm² | 76 A | 59 A | 4.68 V (2.04%) | 225.3 V | 7.72 V (3.36%) | 163.8 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 3.0 V (1.3%) | 227.0 V | 4.94 V (2.15%) | 104.9 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 2.14 V (0.93%) | 227.9 V | 3.53 V (1.53%) | 74.9 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.5 V (0.65%) | 228.5 V | 2.47 V (1.07%) | 52.4 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 1.07 V (0.47%) | 228.9 V | 1.76 V (0.77%) | 37.4 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.79 V (0.34%) | 229.2 V | 1.3 V (0.57%) | 27.6 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.62 V (0.27%) | 229.4 V | 1.03 V (0.45%) | 21.8 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.5 V (0.22%) | 229.5 V | 0.82 V (0.36%) | 17.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.4 V (0.18%) | 229.6 V | 0.67 V (0.29%) | 14.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.31 V (0.14%) | 229.7 V | 0.51 V (0.22%) | 10.9 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.25 V (0.11%) | 229.8 V | 0.41 V (0.18%) | 8.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.19 V (0.08%) | 229.8 V | 0.31 V (0.13%) | 6.6 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 35 Ampere ved 50 Meter (230V)
Hvilket kabeltværsnit kræves til 35A ved 50 meter (230V)?
Til 35 Ampere over 50 meter ved 230V anbefales 16 mm² kobberkabel (spændingsfald 4.68V / 2.04%).
Hvor mange kW svarer 35A ved 230V til?
Det svarer til 8.05 kW med en anbefalet sikring på 35A.
Related Lengths & Currents (230V)
35A · 5m (230V)35A · 10m (230V)35A · 15m (230V)35A · 20m (230V)35A · 25m (230V)35A · 30m (230V)35A · 35m (230V)35A · 40m (230V)35A · 45m (230V)35A · 60m (230V)35A · 70m (230V)10A · 50m (230V)16A · 50m (230V)20A · 50m (230V)25A · 50m (230V)32A · 50m (230V)40A · 50m (230V)50A · 50m (230V)63A · 50m (230V)80A · 50m (230V)100A · 50m (230V)125A · 50m (230V)160A · 50m (230V)200A · 50m (230V)