Kabeltværsnit for 350 Ampere ved 40 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 350 A over 40 m ved 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 2.8V (0.7%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 2.85V (0.71%)
Voltage at Load397.2 VLine Loss: 1700.4 W
Max Power & Breaker242.49 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A345.95 V (86.49%)54.1 V570.65 V (142.66%)209720.0 WDrop High
2.5 mm²24 A18 A207.57 V (51.89%)192.4 V342.39 V (85.6%)125832.0 WDrop High
4 mm²32 A25 A129.73 V (32.43%)270.3 V213.99 V (53.5%)78645.0 WDrop High
6 mm²41 A32 A86.49 V (21.62%)313.5 V142.66 V (35.67%)52430.0 WDrop High
10 mm²57 A44 A51.89 V (12.97%)348.1 V85.6 V (21.4%)31458.0 WDrop High
16 mm²76 A59 A32.43 V (8.11%)367.6 V53.5 V (13.37%)19661.2 WDrop High
25 mm²101 A78 A20.76 V (5.19%)379.2 V34.24 V (8.56%)12583.2 WDrop High
35 mm²125 A97 A14.83 V (3.71%)385.2 V24.46 V (6.11%)8988.0 WDrop High
50 mm²151 A118 A10.38 V (2.59%)389.6 V17.12 V (4.28%)6291.6 WDrop High
70 mm²192 A150 A7.41 V (1.85%)392.6 V12.23 V (3.06%)4494.0 WDrop High
95 mm²232 A181 A5.46 V (1.37%)394.5 V9.01 V (2.25%)3311.4 WDrop High
120 mm²269 A210 A4.32 V (1.08%)395.7 V7.13 V (1.78%)2621.5 WDrop High
150 mm²309 A241 A3.46 V (0.86%)396.5 V5.71 V (1.43%)2097.2 WDrop High
185 mm²353 A275 A2.8 V (0.7%)397.2 V4.63 V (1.16%)1700.4 W✓ OK (≤3%)
240 mm²415 A324 A2.16 V (0.54%)397.8 V3.57 V (0.89%)1310.8 W✓ OK (≤3%)
300 mm²477 A372 A1.73 V (0.43%)398.3 V2.85 V (0.71%)1048.6 W✓ OK (≤3%)
400 mm²570 A445 A1.3 V (0.32%)398.7 V2.14 V (0.53%)786.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 350 Ampere ved 40 Meter (400V)

Hvilket kabeltværsnit kræves til 350A ved 40 meter (400V)?

Til 350 Ampere over 40 meter ved 400V anbefales 185 mm² kobberkabel (spændingsfald 2.8V / 0.7%).

Hvor mange kW svarer 350A ved 400V til?

Det svarer til 242.49 kW med en anbefalet sikring på 350A.