⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 350 Ampere ved 90 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 350 A over 90 m ved 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 6.31V (1.58%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 6.42V (1.6%)
Voltage at Load393.7 VLine Loss: 3826.0 W
Max Power & Breaker242.49 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A778.38 V (194.6%)0.0 V1283.97 V (320.99%)471870.0 WDrop High
2.5 mm²24 A18 A467.03 V (116.76%)0.0 V770.38 V (192.6%)283122.0 WDrop High
4 mm²32 A25 A291.89 V (72.97%)108.1 V481.49 V (120.37%)176951.2 WDrop High
6 mm²41 A32 A194.6 V (48.65%)205.4 V320.99 V (80.25%)117967.5 WDrop High
10 mm²57 A44 A116.76 V (29.19%)283.2 V192.6 V (48.15%)70780.5 WDrop High
16 mm²76 A59 A72.97 V (18.24%)327.0 V120.37 V (30.09%)44237.8 WDrop High
25 mm²101 A78 A46.7 V (11.68%)353.3 V77.04 V (19.26%)28312.2 WDrop High
35 mm²125 A97 A33.36 V (8.34%)366.6 V55.03 V (13.76%)20223.0 WDrop High
50 mm²151 A118 A23.35 V (5.84%)376.6 V38.52 V (9.63%)14156.1 WDrop High
70 mm²192 A150 A16.68 V (4.17%)383.3 V27.51 V (6.88%)10111.5 WDrop High
95 mm²232 A181 A12.29 V (3.07%)387.7 V20.27 V (5.07%)7450.6 WDrop High
120 mm²269 A210 A9.73 V (2.43%)390.3 V16.05 V (4.01%)5898.4 WDrop High
150 mm²309 A241 A7.78 V (1.95%)392.2 V12.84 V (3.21%)4718.7 WDrop High
185 mm²353 A275 A6.31 V (1.58%)393.7 V10.41 V (2.6%)3826.0 W✓ OK (≤3%)
240 mm²415 A324 A4.86 V (1.22%)395.1 V8.02 V (2.01%)2949.2 W✓ OK (≤3%)
300 mm²477 A372 A3.89 V (0.97%)396.1 V6.42 V (1.6%)2359.3 W✓ OK (≤3%)
400 mm²570 A445 A2.92 V (0.73%)397.1 V4.81 V (1.2%)1769.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 350 Ampere ved 90 Meter (400V)

Hvilket kabeltværsnit kræves til 350A ved 90 meter (400V)?

Til 350 Ampere over 90 meter ved 400V anbefales 185 mm² kobberkabel (spændingsfald 6.31V / 1.58%).

Hvor mange kW svarer 350A ved 400V til?

Det svarer til 242.49 kW med en anbefalet sikring på 350A.