Kabeltværsnit for 375 Ampere ved 150 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 375 A over 150 m ved 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 8.69V (2.17%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.6V (2.15%)
Voltage at Load391.3 VLine Loss: 5642.6 W
Max Power & Breaker259.81 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1389.97 V (347.49%)0.0 V2292.8 V (573.2%)902812.5 WDrop High
2.5 mm²24 A18 A833.98 V (208.5%)0.0 V1375.68 V (343.92%)541687.5 WDrop High
4 mm²32 A25 A521.24 V (130.31%)0.0 V859.8 V (214.95%)338554.7 WDrop High
6 mm²41 A32 A347.49 V (86.87%)52.5 V573.2 V (143.3%)225703.1 WDrop High
10 mm²57 A44 A208.5 V (52.12%)191.5 V343.92 V (85.98%)135421.9 WDrop High
16 mm²76 A59 A130.31 V (32.58%)269.7 V214.95 V (53.74%)84638.7 WDrop High
25 mm²101 A78 A83.4 V (20.85%)316.6 V137.57 V (34.39%)54168.7 WDrop High
35 mm²125 A97 A59.57 V (14.89%)340.4 V98.26 V (24.57%)38692.0 WDrop High
50 mm²151 A118 A41.7 V (10.42%)358.3 V68.78 V (17.2%)27084.4 WDrop High
70 mm²192 A150 A29.79 V (7.45%)370.2 V49.13 V (12.28%)19346.0 WDrop High
95 mm²232 A181 A21.95 V (5.49%)378.1 V36.2 V (9.05%)14254.9 WDrop High
120 mm²269 A210 A17.37 V (4.34%)382.6 V28.66 V (7.17%)11285.2 WDrop High
150 mm²309 A241 A13.9 V (3.47%)386.1 V22.93 V (5.73%)9028.1 WDrop High
185 mm²353 A275 A11.27 V (2.82%)388.7 V18.59 V (4.65%)7320.1 WDrop High
240 mm²415 A324 A8.69 V (2.17%)391.3 V14.33 V (3.58%)5642.6 W✓ OK (≤3%)
300 mm²477 A372 A6.95 V (1.74%)393.1 V11.46 V (2.87%)4514.1 W✓ OK (≤3%)
400 mm²570 A445 A5.21 V (1.3%)394.8 V8.6 V (2.15%)3385.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 375 Ampere ved 150 Meter (400V)

Hvilket kabeltværsnit kræves til 375A ved 150 meter (400V)?

Til 375 Ampere over 150 meter ved 400V anbefales 240 mm² kobberkabel (spændingsfald 8.69V / 2.17%).

Hvor mange kW svarer 375A ved 400V til?

Det svarer til 259.81 kW med en anbefalet sikring på 400A.