⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 400 Ampere ved 20 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 400 A over 20 m ved 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 1.24V (0.31%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.22V (0.31%)
Voltage at Load398.8 VLine Loss: 856.0 W
Max Power & Breaker277.13 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A197.68 V (49.42%)202.3 V326.09 V (81.52%)136960.0 WDrop High
2.5 mm²24 A18 A118.61 V (29.65%)281.4 V195.65 V (48.91%)82176.0 WDrop High
4 mm²32 A25 A74.13 V (18.53%)325.9 V122.28 V (30.57%)51360.0 WDrop High
6 mm²41 A32 A49.42 V (12.36%)350.6 V81.52 V (20.38%)34240.0 WDrop High
10 mm²57 A44 A29.65 V (7.41%)370.3 V48.91 V (12.23%)20544.0 WDrop High
16 mm²76 A59 A18.53 V (4.63%)381.5 V30.57 V (7.64%)12840.0 WDrop High
25 mm²101 A78 A11.86 V (2.97%)388.1 V19.57 V (4.89%)8217.6 WDrop High
35 mm²125 A97 A8.47 V (2.12%)391.5 V13.98 V (3.49%)5869.7 WDrop High
50 mm²151 A118 A5.93 V (1.48%)394.1 V9.78 V (2.45%)4108.8 WDrop High
70 mm²192 A150 A4.24 V (1.06%)395.8 V6.99 V (1.75%)2934.9 WDrop High
95 mm²232 A181 A3.12 V (0.78%)396.9 V5.15 V (1.29%)2162.5 WDrop High
120 mm²269 A210 A2.47 V (0.62%)397.5 V4.08 V (1.02%)1712.0 WDrop High
150 mm²309 A241 A1.98 V (0.49%)398.0 V3.26 V (0.82%)1369.6 WDrop High
185 mm²353 A275 A1.6 V (0.4%)398.4 V2.64 V (0.66%)1110.5 WDrop High
240 mm²415 A324 A1.24 V (0.31%)398.8 V2.04 V (0.51%)856.0 W✓ OK (≤3%)
300 mm²477 A372 A0.99 V (0.25%)399.0 V1.63 V (0.41%)684.8 W✓ OK (≤3%)
400 mm²570 A445 A0.74 V (0.19%)399.3 V1.22 V (0.31%)513.6 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 400 Ampere ved 20 Meter (400V)

Hvilket kabeltværsnit kræves til 400A ved 20 meter (400V)?

Til 400 Ampere over 20 meter ved 400V anbefales 240 mm² kobberkabel (spændingsfald 1.24V / 0.31%).

Hvor mange kW svarer 400A ved 400V til?

Det svarer til 277.13 kW med en anbefalet sikring på 400A.