Kabeltværsnit for 400 Ampere ved 30 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 400 A over 30 m ved 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 1.85V (0.46%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.83V (0.46%)
Voltage at Load398.1 VLine Loss: 1284.0 W
Max Power & Breaker277.13 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A296.53 V (74.13%)103.5 V489.13 V (122.28%)205440.0 WDrop High
2.5 mm²24 A18 A177.92 V (44.48%)222.1 V293.48 V (73.37%)123264.0 WDrop High
4 mm²32 A25 A111.2 V (27.8%)288.8 V183.42 V (45.86%)77040.0 WDrop High
6 mm²41 A32 A74.13 V (18.53%)325.9 V122.28 V (30.57%)51360.0 WDrop High
10 mm²57 A44 A44.48 V (11.12%)355.5 V73.37 V (18.34%)30816.0 WDrop High
16 mm²76 A59 A27.8 V (6.95%)372.2 V45.86 V (11.46%)19260.0 WDrop High
25 mm²101 A78 A17.79 V (4.45%)382.2 V29.35 V (7.34%)12326.4 WDrop High
35 mm²125 A97 A12.71 V (3.18%)387.3 V20.96 V (5.24%)8804.6 WDrop High
50 mm²151 A118 A8.9 V (2.22%)391.1 V14.67 V (3.67%)6163.2 WDrop High
70 mm²192 A150 A6.35 V (1.59%)393.6 V10.48 V (2.62%)4402.3 WDrop High
95 mm²232 A181 A4.68 V (1.17%)395.3 V7.72 V (1.93%)3243.8 WDrop High
120 mm²269 A210 A3.71 V (0.93%)396.3 V6.11 V (1.53%)2568.0 WDrop High
150 mm²309 A241 A2.97 V (0.74%)397.0 V4.89 V (1.22%)2054.4 WDrop High
185 mm²353 A275 A2.4 V (0.6%)397.6 V3.97 V (0.99%)1665.7 WDrop High
240 mm²415 A324 A1.85 V (0.46%)398.1 V3.06 V (0.76%)1284.0 W✓ OK (≤3%)
300 mm²477 A372 A1.48 V (0.37%)398.5 V2.45 V (0.61%)1027.2 W✓ OK (≤3%)
400 mm²570 A445 A1.11 V (0.28%)398.9 V1.83 V (0.46%)770.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 400 Ampere ved 30 Meter (400V)

Hvilket kabeltværsnit kræves til 400A ved 30 meter (400V)?

Til 400 Ampere over 30 meter ved 400V anbefales 240 mm² kobberkabel (spændingsfald 1.85V / 0.46%).

Hvor mange kW svarer 400A ved 400V til?

Det svarer til 277.13 kW med en anbefalet sikring på 400A.