Kabeltværsnit for 45 Ampere ved 15 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 45 A over 15 m ved 400V.
Copper Cable (≤3% Drop)10 mm²Drop: 2.5V (0.63%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 2.58V (0.64%)
Voltage at Load397.5 VLine Loss: 195.0 W
Max Power & Breaker31.18 kW45A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 15m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 16.68 V (4.17%) | 383.3 V | 27.51 V (6.88%) | 1300.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 10.01 V (2.5%) | 390.0 V | 16.51 V (4.13%) | 780.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 6.25 V (1.56%) | 393.7 V | 10.32 V (2.58%) | 487.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 4.17 V (1.04%) | 395.8 V | 6.88 V (1.72%) | 325.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 2.5 V (0.63%) | 397.5 V | 4.13 V (1.03%) | 195.0 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.56 V (0.39%) | 398.4 V | 2.58 V (0.64%) | 121.9 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 1.0 V (0.25%) | 399.0 V | 1.65 V (0.41%) | 78.0 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.71 V (0.18%) | 399.3 V | 1.18 V (0.29%) | 55.7 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.5 V (0.13%) | 399.5 V | 0.83 V (0.21%) | 39.0 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.36 V (0.09%) | 399.6 V | 0.59 V (0.15%) | 27.9 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.26 V (0.07%) | 399.7 V | 0.43 V (0.11%) | 20.5 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.21 V (0.05%) | 399.8 V | 0.34 V (0.09%) | 16.3 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.17 V (0.04%) | 399.8 V | 0.28 V (0.07%) | 13.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.14 V (0.03%) | 399.9 V | 0.22 V (0.06%) | 10.5 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.1 V (0.03%) | 399.9 V | 0.17 V (0.04%) | 8.1 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.08 V (0.02%) | 399.9 V | 0.14 V (0.03%) | 6.5 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.06 V (0.02%) | 399.9 V | 0.1 V (0.03%) | 4.9 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 45 Ampere ved 15 Meter (400V)
Hvilket kabeltværsnit kræves til 45A ved 15 meter (400V)?
Til 45 Ampere over 15 meter ved 400V anbefales 10 mm² kobberkabel (spændingsfald 2.5V / 0.63%).
Hvor mange kW svarer 45A ved 400V til?
Det svarer til 31.18 kW med en anbefalet sikring på 45A.
Related Lengths & Currents (400V)
45A · 5m (400V)45A · 10m (400V)45A · 20m (400V)45A · 25m (400V)45A · 30m (400V)45A · 35m (400V)45A · 40m (400V)45A · 45m (400V)45A · 50m (400V)45A · 60m (400V)45A · 70m (400V)10A · 15m (400V)16A · 15m (400V)20A · 15m (400V)25A · 15m (400V)32A · 15m (400V)40A · 15m (400V)50A · 15m (400V)63A · 15m (400V)80A · 15m (400V)100A · 15m (400V)125A · 15m (400V)160A · 15m (400V)200A · 15m (400V)