Kabeltværsnit for 45 Ampere ved 5 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 45 A over 5 m ved 400V.
Copper Cable (≤3% Drop)10 mm²Drop: 0.83V (0.21%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 0.86V (0.21%)
Voltage at Load399.2 VLine Loss: 65.0 W
Max Power & Breaker31.18 kW45A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 5.56 V (1.39%) | 394.4 V | 9.17 V (2.29%) | 433.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 3.34 V (0.83%) | 396.7 V | 5.5 V (1.38%) | 260.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 2.08 V (0.52%) | 397.9 V | 3.44 V (0.86%) | 162.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 1.39 V (0.35%) | 398.6 V | 2.29 V (0.57%) | 108.3 W | Drop High |
| 10 mm² | 57 A | 44 A | 0.83 V (0.21%) | 399.2 V | 1.38 V (0.34%) | 65.0 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.52 V (0.13%) | 399.5 V | 0.86 V (0.21%) | 40.6 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.33 V (0.08%) | 399.7 V | 0.55 V (0.14%) | 26.0 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.24 V (0.06%) | 399.8 V | 0.39 V (0.1%) | 18.6 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.17 V (0.04%) | 399.8 V | 0.28 V (0.07%) | 13.0 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.12 V (0.03%) | 399.9 V | 0.2 V (0.05%) | 9.3 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.09 V (0.02%) | 399.9 V | 0.14 V (0.04%) | 6.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.07 V (0.02%) | 399.9 V | 0.11 V (0.03%) | 5.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.06 V (0.01%) | 399.9 V | 0.09 V (0.02%) | 4.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.05 V (0.01%) | 400.0 V | 0.07 V (0.02%) | 3.5 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.03 V (0.01%) | 400.0 V | 0.06 V (0.01%) | 2.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.03 V (0.01%) | 400.0 V | 0.05 V (0.01%) | 2.2 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.02 V (0.01%) | 400.0 V | 0.03 V (0.01%) | 1.6 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 45 Ampere ved 5 Meter (400V)
Hvilket kabeltværsnit kræves til 45A ved 5 meter (400V)?
Til 45 Ampere over 5 meter ved 400V anbefales 10 mm² kobberkabel (spændingsfald 0.83V / 0.21%).
Hvor mange kW svarer 45A ved 400V til?
Det svarer til 31.18 kW med en anbefalet sikring på 45A.
Related Lengths & Currents (400V)
45A · 10m (400V)45A · 15m (400V)45A · 20m (400V)45A · 25m (400V)45A · 30m (400V)45A · 35m (400V)45A · 40m (400V)45A · 45m (400V)45A · 50m (400V)45A · 60m (400V)45A · 70m (400V)10A · 5m (400V)16A · 5m (400V)20A · 5m (400V)25A · 5m (400V)32A · 5m (400V)40A · 5m (400V)50A · 5m (400V)63A · 5m (400V)80A · 5m (400V)100A · 5m (400V)125A · 5m (400V)160A · 5m (400V)200A · 5m (400V)