Kabeltværsnit for 475 Ampere ved 20 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 475 A over 20 m ved 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 1.17V (0.29%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.45V (0.36%)
Voltage at Load398.8 VLine Loss: 965.7 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A234.75 V (58.69%)165.2 V387.23 V (96.81%)193135.0 WDrop High
2.5 mm²24 A18 A140.85 V (35.21%)259.1 V232.34 V (58.08%)115881.0 WDrop High
4 mm²32 A25 A88.03 V (22.01%)312.0 V145.21 V (36.3%)72425.6 WDrop High
6 mm²41 A32 A58.69 V (14.67%)341.3 V96.81 V (24.2%)48283.8 WDrop High
10 mm²57 A44 A35.21 V (8.8%)364.8 V58.08 V (14.52%)28970.2 WDrop High
16 mm²76 A59 A22.01 V (5.5%)378.0 V36.3 V (9.08%)18106.4 WDrop High
25 mm²101 A78 A14.09 V (3.52%)385.9 V23.23 V (5.81%)11588.1 WDrop High
35 mm²125 A97 A10.06 V (2.52%)389.9 V16.6 V (4.15%)8277.2 WDrop High
50 mm²151 A118 A7.04 V (1.76%)393.0 V11.62 V (2.9%)5794.1 WDrop High
70 mm²192 A150 A5.03 V (1.26%)395.0 V8.3 V (2.07%)4138.6 WDrop High
95 mm²232 A181 A3.71 V (0.93%)396.3 V6.11 V (1.53%)3049.5 WDrop High
120 mm²269 A210 A2.93 V (0.73%)397.1 V4.84 V (1.21%)2414.2 WDrop High
150 mm²309 A241 A2.35 V (0.59%)397.7 V3.87 V (0.97%)1931.3 WDrop High
185 mm²353 A275 A1.9 V (0.48%)398.1 V3.14 V (0.78%)1566.0 WDrop High
240 mm²415 A324 A1.47 V (0.37%)398.5 V2.42 V (0.61%)1207.1 WDrop High
300 mm²477 A372 A1.17 V (0.29%)398.8 V1.94 V (0.48%)965.7 W✓ OK (≤3%)
400 mm²570 A445 A0.88 V (0.22%)399.1 V1.45 V (0.36%)724.3 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 475 Ampere ved 20 Meter (400V)

Hvilket kabeltværsnit kræves til 475A ved 20 meter (400V)?

Til 475 Ampere over 20 meter ved 400V anbefales 300 mm² kobberkabel (spændingsfald 1.17V / 0.29%).

Hvor mange kW svarer 475A ved 400V til?

Det svarer til 329.09 kW med en anbefalet sikring på 500A.