⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 475 Ampere ved 25 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 475 A over 25 m ved 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 1.47V (0.37%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.82V (0.45%)
Voltage at Load398.5 VLine Loss: 1207.1 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A293.44 V (73.36%)106.6 V484.04 V (121.01%)241418.7 WDrop High
2.5 mm²24 A18 A176.06 V (44.02%)223.9 V290.42 V (72.61%)144851.2 WDrop High
4 mm²32 A25 A110.04 V (27.51%)290.0 V181.51 V (45.38%)90532.0 WDrop High
6 mm²41 A32 A73.36 V (18.34%)326.6 V121.01 V (30.25%)60354.7 WDrop High
10 mm²57 A44 A44.02 V (11.0%)356.0 V72.61 V (18.15%)36212.8 WDrop High
16 mm²76 A59 A27.51 V (6.88%)372.5 V45.38 V (11.34%)22633.0 WDrop High
25 mm²101 A78 A17.61 V (4.4%)382.4 V29.04 V (7.26%)14485.1 WDrop High
35 mm²125 A97 A12.58 V (3.14%)387.4 V20.74 V (5.19%)10346.5 WDrop High
50 mm²151 A118 A8.8 V (2.2%)391.2 V14.52 V (3.63%)7242.6 WDrop High
70 mm²192 A150 A6.29 V (1.57%)393.7 V10.37 V (2.59%)5173.3 WDrop High
95 mm²232 A181 A4.63 V (1.16%)395.4 V7.64 V (1.91%)3811.9 WDrop High
120 mm²269 A210 A3.67 V (0.92%)396.3 V6.05 V (1.51%)3017.7 WDrop High
150 mm²309 A241 A2.93 V (0.73%)397.1 V4.84 V (1.21%)2414.2 WDrop High
185 mm²353 A275 A2.38 V (0.59%)397.6 V3.92 V (0.98%)1957.4 WDrop High
240 mm²415 A324 A1.83 V (0.46%)398.2 V3.03 V (0.76%)1508.9 WDrop High
300 mm²477 A372 A1.47 V (0.37%)398.5 V2.42 V (0.61%)1207.1 W✓ OK (≤3%)
400 mm²570 A445 A1.1 V (0.28%)398.9 V1.82 V (0.45%)905.3 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 475 Ampere ved 25 Meter (400V)

Hvilket kabeltværsnit kræves til 475A ved 25 meter (400V)?

Til 475 Ampere over 25 meter ved 400V anbefales 300 mm² kobberkabel (spændingsfald 1.47V / 0.37%).

Hvor mange kW svarer 475A ved 400V til?

Det svarer til 329.09 kW med en anbefalet sikring på 500A.