Kabeltværsnit for 5 Ampere ved 250 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 5 A over 250 m ved 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 11.58V (2.9%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 7.64V (1.91%)
Voltage at Load388.4 VLine Loss: 100.3 W
Max Power & Breaker3.46 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A30.89 V (7.72%)369.1 V50.95 V (12.74%)267.5 WDrop High
2.5 mm²24 A18 A18.53 V (4.63%)381.5 V30.57 V (7.64%)160.5 W~ ≤5%
4 mm²32 A25 A11.58 V (2.9%)388.4 V19.11 V (4.78%)100.3 W✓ OK (≤3%)
6 mm²41 A32 A7.72 V (1.93%)392.3 V12.74 V (3.18%)66.9 W✓ OK (≤3%)
10 mm²57 A44 A4.63 V (1.16%)395.4 V7.64 V (1.91%)40.1 W✓ OK (≤3%)
16 mm²76 A59 A2.9 V (0.72%)397.1 V4.78 V (1.19%)25.1 W✓ OK (≤3%)
25 mm²101 A78 A1.85 V (0.46%)398.1 V3.06 V (0.76%)16.1 W✓ OK (≤3%)
35 mm²125 A97 A1.32 V (0.33%)398.7 V2.18 V (0.55%)11.5 W✓ OK (≤3%)
50 mm²151 A118 A0.93 V (0.23%)399.1 V1.53 V (0.38%)8.0 W✓ OK (≤3%)
70 mm²192 A150 A0.66 V (0.17%)399.3 V1.09 V (0.27%)5.7 W✓ OK (≤3%)
95 mm²232 A181 A0.49 V (0.12%)399.5 V0.8 V (0.2%)4.2 W✓ OK (≤3%)
120 mm²269 A210 A0.39 V (0.1%)399.6 V0.64 V (0.16%)3.3 W✓ OK (≤3%)
150 mm²309 A241 A0.31 V (0.08%)399.7 V0.51 V (0.13%)2.7 W✓ OK (≤3%)
185 mm²353 A275 A0.25 V (0.06%)399.7 V0.41 V (0.1%)2.2 W✓ OK (≤3%)
240 mm²415 A324 A0.19 V (0.05%)399.8 V0.32 V (0.08%)1.7 W✓ OK (≤3%)
300 mm²477 A372 A0.15 V (0.04%)399.8 V0.25 V (0.06%)1.3 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.03%)399.9 V0.19 V (0.05%)1.0 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 5 Ampere ved 250 Meter (400V)

Hvilket kabeltværsnit kræves til 5A ved 250 meter (400V)?

Til 5 Ampere over 250 meter ved 400V anbefales 4 mm² kobberkabel (spændingsfald 11.58V / 2.9%).

Hvor mange kW svarer 5A ved 400V til?

Det svarer til 3.46 kW med en anbefalet sikring på 6A.