Kabeltværsnit for 60 Ampere ved 5 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 60 A over 5 m ved 400V.
Copper Cable (≤3% Drop)16 mm²Drop: 0.69V (0.17%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 0.73V (0.18%)
Voltage at Load399.3 VLine Loss: 72.2 W
Max Power & Breaker41.57 kW60A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 7.41 V (1.85%) | 392.6 V | 12.23 V (3.06%) | 770.4 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 4.45 V (1.11%) | 395.6 V | 7.34 V (1.83%) | 462.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 2.78 V (0.69%) | 397.2 V | 4.59 V (1.15%) | 288.9 W | Drop High |
| 6 mm² | 41 A | 32 A | 1.85 V (0.46%) | 398.1 V | 3.06 V (0.76%) | 192.6 W | Drop High |
| 10 mm² | 57 A | 44 A | 1.11 V (0.28%) | 398.9 V | 1.83 V (0.46%) | 115.6 W | Drop High |
| 16 mm² | 76 A | 59 A | 0.69 V (0.17%) | 399.3 V | 1.15 V (0.29%) | 72.2 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.44 V (0.11%) | 399.6 V | 0.73 V (0.18%) | 46.2 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.32 V (0.08%) | 399.7 V | 0.52 V (0.13%) | 33.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.22 V (0.06%) | 399.8 V | 0.37 V (0.09%) | 23.1 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.16 V (0.04%) | 399.8 V | 0.26 V (0.07%) | 16.5 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.12 V (0.03%) | 399.9 V | 0.19 V (0.05%) | 12.2 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.09 V (0.02%) | 399.9 V | 0.15 V (0.04%) | 9.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.07 V (0.02%) | 399.9 V | 0.12 V (0.03%) | 7.7 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.06 V (0.02%) | 399.9 V | 0.1 V (0.02%) | 6.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.05 V (0.01%) | 400.0 V | 0.08 V (0.02%) | 4.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.04 V (0.01%) | 400.0 V | 0.06 V (0.02%) | 3.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.03 V (0.01%) | 400.0 V | 0.05 V (0.01%) | 2.9 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 60 Ampere ved 5 Meter (400V)
Hvilket kabeltværsnit kræves til 60A ved 5 meter (400V)?
Til 60 Ampere over 5 meter ved 400V anbefales 16 mm² kobberkabel (spændingsfald 0.69V / 0.17%).
Hvor mange kW svarer 60A ved 400V til?
Det svarer til 41.57 kW med en anbefalet sikring på 60A.
Related Lengths & Currents (400V)
60A · 10m (400V)60A · 15m (400V)60A · 20m (400V)60A · 25m (400V)60A · 30m (400V)60A · 35m (400V)60A · 40m (400V)60A · 45m (400V)60A · 50m (400V)60A · 60m (400V)60A · 70m (400V)10A · 5m (400V)16A · 5m (400V)20A · 5m (400V)25A · 5m (400V)32A · 5m (400V)40A · 5m (400V)50A · 5m (400V)63A · 5m (400V)80A · 5m (400V)100A · 5m (400V)125A · 5m (400V)160A · 5m (400V)200A · 5m (400V)