Kabeltværsnit for 60 Ampere ved 70 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 60 A over 70 m ved 400V.
Copper Cable (≤3% Drop)16 mm²Drop: 9.73V (2.43%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 10.27V (2.57%)
Voltage at Load390.3 VLine Loss: 1011.1 W
Max Power & Breaker41.57 kW60A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 70m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 103.78 V (25.95%) | 296.2 V | 171.2 V (42.8%) | 10785.6 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 62.27 V (15.57%) | 337.7 V | 102.72 V (25.68%) | 6471.4 W | Drop High |
| 4 mm² | 32 A | 25 A | 38.92 V (9.73%) | 361.1 V | 64.2 V (16.05%) | 4044.6 W | Drop High |
| 6 mm² | 41 A | 32 A | 25.95 V (6.49%) | 374.1 V | 42.8 V (10.7%) | 2696.4 W | Drop High |
| 10 mm² | 57 A | 44 A | 15.57 V (3.89%) | 384.4 V | 25.68 V (6.42%) | 1617.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 9.73 V (2.43%) | 390.3 V | 16.05 V (4.01%) | 1011.1 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 6.23 V (1.56%) | 393.8 V | 10.27 V (2.57%) | 647.1 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 4.45 V (1.11%) | 395.6 V | 7.34 V (1.83%) | 462.2 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 3.11 V (0.78%) | 396.9 V | 5.14 V (1.28%) | 323.6 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 2.22 V (0.56%) | 397.8 V | 3.67 V (0.92%) | 231.1 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.64 V (0.41%) | 398.4 V | 2.7 V (0.68%) | 170.3 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.3 V (0.32%) | 398.7 V | 2.14 V (0.53%) | 134.8 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.04 V (0.26%) | 399.0 V | 1.71 V (0.43%) | 107.9 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.84 V (0.21%) | 399.2 V | 1.39 V (0.35%) | 87.5 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.65 V (0.16%) | 399.4 V | 1.07 V (0.27%) | 67.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.52 V (0.13%) | 399.5 V | 0.86 V (0.21%) | 53.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.39 V (0.1%) | 399.6 V | 0.64 V (0.16%) | 40.4 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 60 Ampere ved 70 Meter (400V)
Hvilket kabeltværsnit kræves til 60A ved 70 meter (400V)?
Til 60 Ampere over 70 meter ved 400V anbefales 16 mm² kobberkabel (spændingsfald 9.73V / 2.43%).
Hvor mange kW svarer 60A ved 400V til?
Det svarer til 41.57 kW med en anbefalet sikring på 60A.
Related Lengths & Currents (400V)
60A · 5m (400V)60A · 10m (400V)60A · 15m (400V)60A · 20m (400V)60A · 25m (400V)60A · 30m (400V)60A · 35m (400V)60A · 40m (400V)60A · 45m (400V)60A · 50m (400V)60A · 60m (400V)10A · 70m (400V)16A · 70m (400V)20A · 70m (400V)25A · 70m (400V)32A · 70m (400V)40A · 70m (400V)50A · 70m (400V)63A · 70m (400V)80A · 70m (400V)100A · 70m (400V)125A · 70m (400V)160A · 70m (400V)200A · 70m (400V)