Kabeltværsnit for 60 Ampere ved 500 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 60 A over 500 m ved 230V.

Copper Cable (≤3% Drop)240 mm²Drop: 5.35V (2.33%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.29V (2.3%)
Voltage at Load224.7 VLine Loss: 321.0 W
Max Power & Breaker13.8 kW60A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A856.0 V (372.17%)0.0 V1412.0 V (613.91%)51360.0 WDrop High
2.5 mm²24 A18 A513.6 V (223.3%)0.0 V847.2 V (368.35%)30816.0 WDrop High
4 mm²32 A25 A321.0 V (139.57%)0.0 V529.5 V (230.22%)19260.0 WDrop High
6 mm²41 A32 A214.0 V (93.04%)16.0 V353.0 V (153.48%)12840.0 WDrop High
10 mm²57 A44 A128.4 V (55.83%)101.6 V211.8 V (92.09%)7704.0 WDrop High
16 mm²76 A59 A80.25 V (34.89%)149.8 V132.38 V (57.55%)4815.0 WDrop High
25 mm²101 A78 A51.36 V (22.33%)178.6 V84.72 V (36.83%)3081.6 WDrop High
35 mm²125 A97 A36.69 V (15.95%)193.3 V60.51 V (26.31%)2201.1 WDrop High
50 mm²151 A118 A25.68 V (11.17%)204.3 V42.36 V (18.42%)1540.8 WDrop High
70 mm²192 A150 A18.34 V (7.98%)211.7 V30.26 V (13.16%)1100.6 WDrop High
95 mm²232 A181 A13.52 V (5.88%)216.5 V22.29 V (9.69%)810.9 WDrop High
120 mm²269 A210 A10.7 V (4.65%)219.3 V17.65 V (7.67%)642.0 W~ ≤5%
150 mm²309 A241 A8.56 V (3.72%)221.4 V14.12 V (6.14%)513.6 W~ ≤5%
185 mm²353 A275 A6.94 V (3.02%)223.1 V11.45 V (4.98%)416.4 W~ ≤5%
240 mm²415 A324 A5.35 V (2.33%)224.7 V8.82 V (3.84%)321.0 W✓ OK (≤3%)
300 mm²477 A372 A4.28 V (1.86%)225.7 V7.06 V (3.07%)256.8 W✓ OK (≤3%)
400 mm²570 A445 A3.21 V (1.4%)226.8 V5.29 V (2.3%)192.6 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 60 Ampere ved 500 Meter (230V)

Hvilket kabeltværsnit kræves til 60A ved 500 meter (230V)?

Til 60 Ampere over 500 meter ved 230V anbefales 240 mm² kobberkabel (spændingsfald 5.35V / 2.33%).

Hvor mange kW svarer 60A ved 230V til?

Det svarer til 13.8 kW med en anbefalet sikring på 60A.