⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 10 Ampere ved 500 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 10 A over 500 m ved 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 6.11V (2.66%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 5.04V (2.19%)
Voltage at Load223.9 VLine Loss: 61.1 W
Max Power & Breaker2.3 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A142.67 V (62.03%)87.3 V235.33 V (102.32%)1426.7 WDrop High
2.5 mm²24 A18 A85.6 V (37.22%)144.4 V141.2 V (61.39%)856.0 WDrop High
4 mm²32 A25 A53.5 V (23.26%)176.5 V88.25 V (38.37%)535.0 WDrop High
6 mm²41 A32 A35.67 V (15.51%)194.3 V58.83 V (25.58%)356.7 WDrop High
10 mm²57 A44 A21.4 V (9.3%)208.6 V35.3 V (15.35%)214.0 WDrop High
16 mm²76 A59 A13.38 V (5.82%)216.6 V22.06 V (9.59%)133.8 WDrop High
25 mm²101 A78 A8.56 V (3.72%)221.4 V14.12 V (6.14%)85.6 W~ ≤5%
35 mm²125 A97 A6.11 V (2.66%)223.9 V10.09 V (4.39%)61.1 W✓ OK (≤3%)
50 mm²151 A118 A4.28 V (1.86%)225.7 V7.06 V (3.07%)42.8 W✓ OK (≤3%)
70 mm²192 A150 A3.06 V (1.33%)226.9 V5.04 V (2.19%)30.6 W✓ OK (≤3%)
95 mm²232 A181 A2.25 V (0.98%)227.7 V3.72 V (1.62%)22.5 W✓ OK (≤3%)
120 mm²269 A210 A1.78 V (0.78%)228.2 V2.94 V (1.28%)17.8 W✓ OK (≤3%)
150 mm²309 A241 A1.43 V (0.62%)228.6 V2.35 V (1.02%)14.3 W✓ OK (≤3%)
185 mm²353 A275 A1.16 V (0.5%)228.8 V1.91 V (0.83%)11.6 W✓ OK (≤3%)
240 mm²415 A324 A0.89 V (0.39%)229.1 V1.47 V (0.64%)8.9 W✓ OK (≤3%)
300 mm²477 A372 A0.71 V (0.31%)229.3 V1.18 V (0.51%)7.1 W✓ OK (≤3%)
400 mm²570 A445 A0.54 V (0.23%)229.5 V0.88 V (0.38%)5.3 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 10 Ampere ved 500 Meter (230V)

Hvilket kabeltværsnit kræves til 10A ved 500 meter (230V)?

Til 10 Ampere over 500 meter ved 230V anbefales 35 mm² kobberkabel (spændingsfald 6.11V / 2.66%).

Hvor mange kW svarer 10A ved 230V til?

Det svarer til 2.3 kW med en anbefalet sikring på 10A.