Kabeltværsnit for 600 Ampere ved 45 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 600 A over 45 m ved 230V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.45V (0.63%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.77V (2.07%)
Voltage at Load228.6 VLine Loss: 866.7 W
Max Power & Breaker138.0 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 45m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 770.4 V (334.96%) | 0.0 V | 1270.8 V (552.52%) | 462240.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 462.24 V (200.97%) | 0.0 V | 762.48 V (331.51%) | 277344.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 288.9 V (125.61%) | 0.0 V | 476.55 V (207.2%) | 173340.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 192.6 V (83.74%) | 37.4 V | 317.7 V (138.13%) | 115560.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 115.56 V (50.24%) | 114.4 V | 190.62 V (82.88%) | 69336.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 72.22 V (31.4%) | 157.8 V | 119.14 V (51.8%) | 43335.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 46.22 V (20.1%) | 183.8 V | 76.25 V (33.15%) | 27734.4 W | Drop High |
| 35 mm² | 125 A | 97 A | 33.02 V (14.36%) | 197.0 V | 54.46 V (23.68%) | 19810.3 W | Drop High |
| 50 mm² | 151 A | 118 A | 23.11 V (10.05%) | 206.9 V | 38.12 V (16.58%) | 13867.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 16.51 V (7.18%) | 213.5 V | 27.23 V (11.84%) | 9905.1 W | Drop High |
| 95 mm² | 232 A | 181 A | 12.16 V (5.29%) | 217.8 V | 20.07 V (8.72%) | 7298.5 W | Drop High |
| 120 mm² | 269 A | 210 A | 9.63 V (4.19%) | 220.4 V | 15.88 V (6.91%) | 5778.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 7.7 V (3.35%) | 222.3 V | 12.71 V (5.53%) | 4622.4 W | Drop High |
| 185 mm² | 353 A | 275 A | 6.25 V (2.72%) | 223.8 V | 10.3 V (4.48%) | 3747.9 W | Drop High |
| 240 mm² | 415 A | 324 A | 4.81 V (2.09%) | 225.2 V | 7.94 V (3.45%) | 2889.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 3.85 V (1.67%) | 226.1 V | 6.35 V (2.76%) | 2311.2 W | Drop High |
| 400 mm² | 570 A | 445 A | 2.89 V (1.26%) | 227.1 V | 4.77 V (2.07%) | 1733.4 W | Drop High |
FAQ — Kabeltværsnit for 600 Ampere ved 45 Meter (230V)
Hvilket kabeltværsnit kræves til 600A ved 45 meter (230V)?
Til 600 Ampere over 45 meter ved 230V anbefales 2× 400 mm² kobberkabel (spændingsfald 1.45V / 0.63%).
Hvor mange kW svarer 600A ved 230V til?
Det svarer til 138.0 kW med en anbefalet sikring på 600A.
Related Lengths & Currents (230V)
600A · 5m (230V)600A · 10m (230V)600A · 15m (230V)600A · 20m (230V)600A · 25m (230V)600A · 30m (230V)600A · 35m (230V)600A · 40m (230V)600A · 50m (230V)600A · 60m (230V)600A · 70m (230V)10A · 45m (230V)16A · 45m (230V)20A · 45m (230V)25A · 45m (230V)32A · 45m (230V)40A · 45m (230V)50A · 45m (230V)63A · 45m (230V)80A · 45m (230V)100A · 45m (230V)125A · 45m (230V)160A · 45m (230V)200A · 45m (230V)